The ground bonding cable is not included.

Connecting the UPS to utility power

WARNING: To prevent injury from electric shock or damage to the equipment:

Plug the input line cord into a grounded (earthed) electrical outlet that is installed near the equipment and is easily accessible.

Do not disable the grounding plug on the input line cord. The grounding plug is an important safety feature.

Do not use extension cords.

Connect the UPS to a grounded utility power outlet. When the UPS is plugged in, it automatically enters Standby mode and begins charging the batteries.

Connecting devices to the UPS

CAUTION: Do not plug laser printers into the UPS output receptacles. The instantaneous current drawn by this type of printer can overload the UPS.

Before connecting devices:

Verify that the UPS will not overload by checking that the ratings of the devices do not exceed the UPS capacity.

Evenly distribute connected devices to both circuit breakers. See "UPS output specifications (on page 44)" for the maximum current rating for each receptacle.

After verifying that the UPS will not overload:

1.Turn on the circuit breakers for load segments 1 and 2.

NOTE: The circuit breaker for load segment 1 protects the C19 and C13 outlets but not the large output receptacle.

2.Connect the device power cords to the appropriate output receptacles on the rear panel of the UPS.

Installation 22