Output tolerance specifications

Source of power

Regulation

 

 

Utility power (nominal

-10% to +6% of nominal output voltage rating

range)

(within the guidelines of the Computer Business

 

Equipment Manufacturers Association)

 

 

Battery power

±5% of nominal output voltage rating

 

 

Output feature specifications

Feature

Specification

 

 

Online efficiency

94% nominal input voltage

 

 

Voltage wave shape

Sine wave; 5% THD with typical PFC load

 

 

Surge suppression

High-energy 6500 A peak

 

 

Noise filtering

MOVs and line filter for normal and common mode

 

use

 

 

Battery specifications

Feature

Specification

 

 

Type

Each model contains maintenance-free, sealed, valve

 

regulated lead-acid batteries with an 8-year minimum float

 

service life at 25°C (77°F).

 

 

Voltage

The battery modules have a battery string voltage of 240

 

V.

 

 

Charging

Complete charge takes no more than 48 hours.

 

Approximately 3 hours to 80 percent capacity at default

 

nominal utility voltage and no load.

 

 

Battery runtime for NA/JPN model

Load, W (percent)

Estimated battery

Runtime with one ERM

Runtime with two ERMs

 

runtime (minutes)

(minutes)

(minutes)

 

 

 

 

20

59

169

303

 

 

 

 

50

19

61

106

 

 

 

 

80

9

31

60

 

 

 

 

100

7

24

46

 

 

 

 

Battery runtime for INTL model

Load, W (percent)

Estimated battery

Runtime with one ERM

Runtime with two ERMs

 

 

runtime (minutes)

(minutes)

(minutes)

 

 

 

 

 

 

20

49

138

247

 

 

 

 

 

 

 

 

 

Specifications 46