Specifications

UPS physical specifications

Parameter

Value

 

 

Height

13.03 cm (5.13 in)

 

 

Depth

66.04 cm (26 in)

 

 

Width

44.15 cm (17.38 in)

 

 

Weight

68 kg (150 lb)

 

 

ERM physical specifications

Parameter

Value

 

 

Height

13.03 cm (5.13 in)

 

 

Depth

63.83 cm (25.13 in)

 

 

Width

44.45 cm (17.50 in)

 

 

Weight

75 kg (167 lb)

 

 

UPS input specifications

NOTE: An asterisk (*) indicates the default setting.

UPS model

Utility voltage

Available settings

Dedicated

Line cord

 

frequency (Hz)

utility voltage (VAC)

branch circuit

 

 

 

 

rating (A)

 

 

 

 

 

 

R5500

50/60

200/208*, 220, 230,

30

Nondetachable power

NA/JPN

 

240

 

cord with NEMA L6-30

 

 

 

 

plug

 

 

 

 

 

R5500 INTL

50/60

200/208, 220, 230*,

32

Nondetachable power

 

 

240

 

cord with 32 A IEC-309

 

 

 

 

plug

 

 

 

 

 

UPS output specifications

UPS model

Load

Circuit

Output

Maximum current

 

 

segment

breaker

receptacles

 

 

 

 

 

 

 

 

R5500 NA/JPN

1

15 A¹

2 x IEC-320-C19

15 A per receptacle²

 

 

 

 

 

 

 

 

 

 

 

Specifications 44