Load, W (percent)

Estimated battery

Runtime with one ERM

Runtime with two ERMs

 

runtime (minutes)

(minutes)

(minutes)

 

 

 

 

50

15

49

85

 

 

 

 

80

7

25

48

 

 

 

 

100

5

19

36

 

 

 

 

Environmental specifications

Feature

Specification

 

 

Operating temperature

10°C to 40°C (50°F to 104°F); UL-tested at 25°C

 

(77°F)

 

 

Nonoperating

-25°C to 55°C (-13°F to 131°F)

temperature

 

 

 

Relative humidity

20% to 80%; noncondensing

 

 

Operating altitude

Up to 2,000 m (6,600 ft) above sea level

 

 

Nonoperating altitude

15,000 m (49,212 ft) above sea level

 

 

Audible noise

Less than 45 dBA, normal operation

 

Less than 50 dBA, on battery power

 

 

REPO port specifications

The REPO port meets the requirements of NFPA Articles 645-10 and 645-11 for a Disconnecting Means.

Specifications 47