Connecting the REPO port

WARNING: The pins on the REPO port are polarity sensitive. Be sure to verify polarity while connecting the REPO port.

WARNING: To meet the requirements stated in NEC (NFPA 70) Articles 645-10 and 645-11, a UPS installed in a computer equipment room must be connected to a REPO circuit.

IMPORTANT: The remote switch must be in the Off (open) position to enable power to the output receptacles.

NOTE: Wire the connector block using stranded, nonshielded wire (AWG #22 - #18, or equivalent).

Installation 20