OnLine Power
(6002-1646) REV.X8 11
SECTION 2 - INSTALLATION

2-1 SITE PLANNING AND PREPARATION

The Fire Alarm Back-up UPS1 481 is designed for installation ind oors and meets NEMA
specifications for operating te mperature, humidity, and uti lit y voltage. These cabinets are
corrosion resistant and rugg ed. The footprint of the Fire Alar m Bac k - up UPS1481 is less than 6
square feet. Listed below are th e environmental specifications f or t h e Fire Alarm Back-up
UPS1481.
Adequate clearance in the front of t he equipment should be provid ed for service access.
OPERATING ENVIRONMENT
• AMBIENT TEMPERATURE 0°C to 49° C
• OPERATING ALTITUDE 1,829 M (6,000 FT) DERATE 10% FOR EACH ADDITIONAL
305 M (1,000 F~) UP TO 2,744 m (9, 000 FT)
• RELATIVE HUMIDITY 0% to 9 5% (non-condensing)
Operating the Fire Alarm Bac k -u p UPS1481 and batteries at eit he r ex t reme of the temperature
range may affect the long-ter m reliability of the system. This is especially true of the sealed,
maintenance-free batteries. Sealed, maintenance-free b at teries are designed to operate at
normal room temperatures (7 2 to 77°F).
STORAGE ENVIRONMENT.
Provide a storage environm ent which meets the following condit i ons:
• AMBIENT TEMPERATURE -30°C to 70°C
RELATIVE HUMIDITY 0% to 95% non-condens ing