OnLine Power

(6002-1646) REV.X8 27

OTHERS ARE CALCULATED VALUES BASED ON THE BATTERY MANUFACTURER'S DATA FOR BACK UP
TIME.
APPENDIX B – Optional Main Input & Main Output Breakers

for various models (*All Values are typi cal as reference only)

TABLE B-1: External Output Breaker (Standard KAIC)

Output Voltages
KVA 120 Vac 240 /120 VAC
3 40 Amps, 120 VAC,
1 Pole, 14 KAIC
OLP P/N: 2025-783 20 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-788
5 70 Amps, 120 VAC,
1 Pole, 14 KAIC
OLP P/N: 2025-997 40 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-791
7.5 100 Amps, 120 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-999 50 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-792
10 125 Amps, 120 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-759 70 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-794
12.5 1750 Amps, 120 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-468 80 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-795
15 200 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-541 100 Amps, 240 VAC,
2 Pole, 10 KAIC
OLP P/N: 2025-797

TABLE B-2: Output Breaker (High KAIC)

Output Voltages
KVA 120 Vac 240 Vac
3 40 Amps, 120 VAC,
1 Pole, 42 KAIC
OLP P/N: 2025-799 20 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-762
5 70 Amps, 120 VAC,
1 Pole, 42 KAIC
OLP P/N: 2025-998 40 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-766
7.5 100 Amps, 120 VAC,
2 Pole, 42 KAIC
OLP P/N: 2025-803 50 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-767
10 125 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-759 70 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-769
12.5 1750 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-468 80 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-770
15 200 Amps, 120 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-541 100 Amps, 240 VAC,
2 Pole, 65 KAIC
OLP P/N: 2025-894