Channels and channel adapters no longer supported on z990

The following channels and/or channel adapters are no longer supported:

Parallel channels - an ESCON converter is required; IBM 9034 or Optica 34600 FXBT

OSA-2 adapters - use equivalent OSA-Express adapt- ers, for FDDI use 1000BASE-T or Gigabit Ethernet with appropriate multi-protocol switch or router

OSA-Express ATM - use 1000BASE-T or Gigabit Ether- net with appropriate multi-protocol switch or router

4-Port ESCON cards - will be replaced with 16-port ESCON cards during upgrade

FICON (pre FICON Express) - will be replaced with FICON Express during upgrade

PCICC - replaced with PCIXCC for most functions

The fi rst ICB-2 or 3 required a slot. The second to the fourth required another slot. The fi fth to the sixth required another slot. (STI - 2/3 cards each supports two ICBs)

Physical Characteristics

z990 Power/Heating/Cooling

System Power Consumption (kW)

Model / Config

1 I/O Cage

2 I/O Cage

3 I/O Cage

A08

5.3

7.8

10.3

B16

7.3

9.8

12.3

C24

9.1

11.6

13.9

D32

10.8

13.3

15.8

Note: Assumes maximum confi guration of I/O Cages 60 amp cords

System Cooling (Air Flow Rate - CFM)

Model / Config

1 I/O Cage

2 I/O Cage

3 I/O Cage

A08

1400

1800

2200

B16

1800

2200

3000

C24

2200

2600

3250

D32

2200

3000

3250

Note: Assumes chilled underfl oor temperature of 24OC and maximum con- fi guration of I/O cages

Heat Output (kBTU/hr)

Model / Config

1 I/O Cage

2 I/O Cage

3 I/O Cage

A08

18.02

26.52

35.02

B16

24.82

33.32

41.82

C24

30.94

39.44

47.26

D32

36.72

45.22

53.72

z990 Dimensions

 

z990

# of Frames

2 Frames

 

IBF contained within 2 frames

Height (w/ covers)

194.1 cm / 76.4 in (40 EIA)

Width (w/ covers)

157.7 cm / 62.1 in (each frame 30.2 in)

Depth (w/ covers)

157.7 cm / 62.1 in

Height Reduction

178.5 cm / 70.3 in (38 EIA)

Width Reduction

None

Machine Area

2.49 sq. meters / 26.78 sq. feet

Service Clearance

5.45 sq. meters / 58.69 sq. feet

 

(IBF contained within the frame)

53