SECTION 4—SAFETY INSPECTION/ TROUBLESHOOTING

SECTION 4—SAFETY INSPECTION/TROUBLESHOOTING

SECTION 4—SAFETY INSPECTION/ TROUBLESHOOTING

NOTE: Every six months or as necessary have a qualified technician perform a thorough inspection and servicing. Routine maintenance will extend the life and efficiency of your tub.

Safety Inspection Checklists

Initially

Ensure that the maximum water supply temperature does not exceed 115° F.

Ensure that the maximum water pressure does not exceed 65 PSI.

Verify the water flow temperature with a separate thermometer.

Visually inspect for cracks in the tub surface.

Ensure that the door handle locks the door closed.

Ensure that the safety pin properly engages the door.

Check that all labels are present and legible. Replace if necessary.

Before Each Use

Disinfect the tub.

Ensure that the maximum water supply temperature does not exceed 115° F.

Ensure that the maximum water pressure does not exceed 65 PSI.

Visually inspect for cracks in the tub surface.

Ensure that the door handle locks the door closed.

Ensure that the safety pin properly engages the door.

Every 80-150 Baths

Perform the heavy duty cleaning procedure on the tub. Refer to warning on page 30.

Every Six Months

Verify the water flow temperature with a separate thermometer.

Check that all labels are present and legible. Replace if necessary.

Clean RADA valve to remove lime deposits.