Jenn-Air W10253462A Calculating Vent System Length, Left or Right Side Venting, A L K J, D C I

Models: W10253462A

1 40
Download 40 pages 44.43 Kb
Page 6
Image 6
Left or Right Side Venting

Left or Right Side Venting

Venting Behind Cabinet Kickplate

A

B

A. Wall cap

B. 6" (15.2 cm) round roof venting

Concrete Slab Installations - Exhaust Through Wall

B

Calculating Vent System Length

IMPORTANT: This range is rated at 60 ft (18.3 m) of straight duct. Low range is up to 30 ft (9.1 m); high range is 31 ft (9.4 m) to 60 ft (18.3 m).

If equivalent duct length exceeds 30 ft (18.3 m), the blower must be converted to high range.

Do not convert to high range for shorter lengths. This will cause excessive noise, conditioned air loss and affect the flame pattern on gas ranges.

To convert blower for high range installations, see the “Install Downdraft System” section.

To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.

Vent Piece

6" (15.2 cm) Round

45° elbow

2.5 ft

 

(0.8 m)

A

L

K

J

D

C

I

E

F

G

H

90° elbow

5.0 ft

 

(1.5 m)

 

 

6" (15.2 cm)

0.0 ft

wall cap

(0.0 m)

A. Wall cap

B. 6" (15.2 cm) round metal vent C. 16" (40.6 cm) maximum

D. 6" (15.2 cm) round PVC sewer pipe E. Concrete slab

F. 6" (15.2 cm) round PVC sewer pipe

G. 6" (15.2 cm) round 90° PVC sewer pipe elbow

H. Tightly pack gravel or sand completely around pipe.

I. 30 ft (9.1 m) max.

J. 6" (15.2 cm) round 90° PVC sewer pipe elbow K. 6" (15.2 cm) round PVC coupling

L. 12" (30.5 cm) minimum

Concrete Slab Installations -

Exhaust Through Window Well

IMPORTANT: Window well installation for electric models only.

 

B

 

 

 

 

 

D

A

 

C

 

 

 

 

E

K

 

H

F

 

G

 

 

 

 

J

I

 

 

 

 

A. Wall cap

B. 12" (30.5 cm) minimum C. Concrete slab

D. 6" (15.2 cm) round PVC sewer pipe E. 6" (15.2 cm) round PVC sewer pipe

F. 6" (15.2 cm) round 90° PVC sewer pipe elbow

G. Tightly pack gravel or sand completely around pipe. H. 42 ft (12.8 m) max.

I. 6" (15.2 cm) round PVC coupling J. 6" (15.2 cm) minimum

K. Window well

3¹⁄₄" x 10" (8.3 cm x 25.4 cm)

4.5 ft

to 6" (15.2 cm) transition

(1.4 m)

 

 

6" (15.2 cm) to 3¹⁄₄" x 10"

1 ft

(8.3 cm x 25.4 cm) transition

(0.3 m)

 

 

3¹⁄₄" x 10" (8.3 cm x 25.4 cm)

5.0 ft

to 6" (15.2 cm) 90° elbow

(1.5 m)

transition

 

 

 

6" (15.2 cm) to 3¹⁄₄" x 10"

5.0 ft

(8.3 cm x 25.4 cm) 90° elbow

(1.5 m)

transition

 

 

 

3¹⁄₄" x 10" (8.3 cm x 25.4 cm)

5.0 ft

90° elbow

(1.5 m)

 

 

3¹⁄₄" x 10" (8.3 cm x 25.4 cm)

12.0 ft

flat elbow

(3.7 m)

 

 

3¹⁄₄" x 10" (8.3 cm x 25.4 cm)

0.0 ft

wall cap

(0.0 m)

6

Page 6
Image 6
Jenn-Air W10253462A installation instructions Calculating Vent System Length, Left or Right Side Venting, A L K J, D C I