ADJUSTMENT OF TEMPERATURE RISE
DANGER
The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations shown in Table 7 “ELECTRICAL AND PERFORMANCE DATA”.
The supply air temperature cannot exceed the “Maximum Supply Air Temperature” specified in these instructions and on the furnace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause pre- mature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or death.
After about 5 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet (1.83 m) from the furnace where they will not be affected by radiant heat. Increase the blower speed to decrease the temperature rise; decrease the blower speed to increase the rise.
VARIABLE SPEED MOTORS
The variable speed motor must be configured so the blower will provide a sufficient airflow so that the furnace operates with in the temperature rise range on the rating plate and within the application limitations shown in Table 7 in these Instructions.
ADJUSTMENT OF FAN CONTROL SETTINGS
Heating Indoor Fan Off Delay
This furnace is equipped with a
BLOWER OFF | HI HEAT DELAY | CONTINUOUS FAN | |
JUMPER | |||
DELAY JUMPER | SPEED JUMPER | ||
|
|
|
|
| LAST |
| CFM | STATUS |
| STAGING | SPEED FAN VSHI HI LO LO | NEUTRALS | |
|
|
|
| ERROR | 180 | 120 | 15 10 OFF 60 90 | 20 | ||||
LOW VOLTAGE |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| |
TERMINALS | Y1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Y Y2 |
|
|
|
|
|
|
|
|
|
| |
| W W1 |
|
|
|
|
|
|
|
|
|
| |
| W2 |
|
|
|
|
|
|
|
|
|
| HUM |
|
|
|
|
|
|
|
|
|
|
|
| |
| R |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LINE |
| G |
|
|
|
|
|
|
|
|
|
|
|
| C |
|
|
|
|
|
|
|
|
|
| XFMR |
|
| BLOWER SPEED |
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||||
| O |
|
| JUMPERS |
|
|
|
|
| EAC | ||
| DHUM |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
| X/L |
| ADJ COOL RELAY HEAT |
|
|
|
|
|
|
| ||
HEAT |
|
| D | D | D |
|
|
|
|
|
|
|
YES |
| C | C | C |
|
|
|
|
|
|
| |
| B | B | B |
|
|
|
|
|
|
| ||
PUMP |
| A | A | A |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| ||
NO |
| DHUM? |
|
|
|
|
|
|
|
|
| |
JUMPER | HEATPUMP |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |||
DEHUMIDISTAT |
|
|
|
|
| COOLING |
|
|
| |||
JUMPER |
|
|
|
|
|
| PROFILE JUMPER |
|
FIGURE 42: Furnace Control Board
Johnson Controls Unitary Products | 33 |