701379-UIM-C-0712

Heating Cycle

When the thermostat switch is set on HEAT and the fan is set on AUTO, and there is a call for heat, a circuit is completed between terminals R and W of the thermostat. When the proper amount of combustion air is being provided, the pressure switch will close, the ignition control pro- vides a 17-second ignitor warm-up period, the gas valve then opens, the gas starts to flow, ignition occurs and the flame sensor begins its sensing function. The blower motor will energize 30 seconds after the gas valve opens, if a flame is detected. Normal furnace operation will continue until the thermostat circuit between R and W is opened, which causes the ignition system and gas valve to de-energize and the burner flames to be extinguished. The vent motor will operate for 15 seconds and the blower motor will operate for the amount of time set by the fan- off delay jumper located on the control board. See Figure 41. The heat- ing cycle is now complete, and ready for the start of the next heating cycle.

If the flame is not detected within 7 seconds of the gas valve opening, the gas valve is shut off and a retry operation begins. Also, if the flame is lost for 2 seconds during the 10-second stabilization period, the gas valve is shut off and a retry operation begins. During a retry operation, the vent motor starts a 15 second inter-purge and the ignitor warm-up time is extended to 27 seconds. If the flame is established for more than 10 seconds after ignition during a retry, the control will clear the ignition attempt (retry) counter. If three retries occur during a call for heat, the furnace will shut down for one hour. If at the end of the one hour shut down there is a call for heat, the furnace will initiate a normal start cycle. If the problem has not been corrected the furnace will again lockout after three retries.

A momentary loss of gas supply, flame blowout, or a faulty flame probe circuit will result in a disruption in the flame and be sensed within 1.0 seconds. The gas valve will de-energize and the control will begin a recycle operation. A normal ignition sequence will begin after a 15 sec- ond inter-purge. If during the five recycles the gas supply does not return, or the fault condition is not corrected the ignition control will lock- out for 60 minutes.

During burner operation, a momentary loss of power for 50 milliseconds or longer will de-energize the gas valve. When the power is restored, the gas valve will remain de-energized and the ignition sequence will immediately restart.

TROUBLESHOOTING

The following visual checks should be made before troubleshooting:

1.Check to see that the power to the furnace and the ignition control module is ON.

2.The manual shut-off valves in the gas line to the furnace must be open.

3.Make sure all wiring connections are secure.

4.Review the sequence of operation. Start the system by setting the thermostat above the room temperature. Observe the system’s response. Then use the troubleshooting section in this manual to check the system’s operation.

Never bypass any safety control to allow furnace operation. To do so will allow furnace to operate under potentially hazardous conditions.

Do not try to repair controls. Replace defective controls with UPG Source 1 Parts.

Never adjust pressure switch to allow furnace operation.

FURNACE CONTROL DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. A blinking LED light on the control board can flash red, green or amber to indicate various conditions. The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED light will indicate the failure code.

The SLOW flash speed is two seconds on and two seconds off.

The other flash codes listed below have the following timing: LED light will turn on for 1/3 second and off for 1/3 second. This pattern will be repeated the number of times equal to the code. There will be a two- second pause between codes. For example, the six red flash code will flash the LED light on and off six times, then will be off for two seconds. This pattern will repeat as long as the fault condition remains. The con- tinuous flash codes listed below will flash the LED light on and off con- tinuously, with no breaks or longer pauses.

SLOW GREEN FLASH: Normal operation, no thermostat calls.

SLOW AMBER FLASH: Normal operation with call for heat.

LED STEADY OFF – If the LED light does not flash at all, check for power to the board and check for a blown fuse on the board. If the board is properly powered and the fuse is not blown, the control board may need to be replaced.

STEADY ON ANY COLOR: Control failure. Turn power to the furnace off and back on. If the fault code returns, the control board must be replaced. The control board is not field-repairable.

CONTINUOUS AMBER FLASH: Flame sense current is below 1.5 microamps. Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

1 RED FLASH: This indicates that flame was sensed when there was not a call for heat. The control will turn on both the inducer motor and supply air blower. Check for a leaking or slow-closing gas valve.

2 RED FLASHES: This indicates that the pressure switch is closed when it should be open. The control confirms that the pressure switch contacts are open at the beginning of each heat cycle and will not let the ignition sequence continue if the pressure switch contacts are closed when they should be open. Check for a faulty pressure switch or miswiring.

3 RED FLASHES: This indicates the pressure switch contacts are open when they should be closed. Check for faulty inducer, blocked vent pipe, broken pressure switch hose, disconnected pressure switch or inducer wires or faulty pressure switch.

4 RED FLASHES: This indicates that the main limit switch has opened its normally closed contacts. The control will turn on the supply air blower and inducer. Check for a dirty filter, improperly sized duct sys- tem, incorrect blower speed setting, incorrect firing rate, loose limit switch wiring or faulty blower motor.

If the limit switch has not closed within five minutes, the control will assume that the blower is not functioning, will start a hard lockout and will begin to flash the 11 Red Flashes error code. If, after fifteen min- utes, the main limit still has not closed, the control will assume that a manual-reset rollout switch has opened and will begin to flash the 5 Red Flash error code. See the description of “5 Red Flashes” and “11Red Flashes” below.

If the main limit switch opens five times within a single call for heat, the control will indicate 4 Red Flashes and will enter a one-hour soft lock- out.

36

Johnson Controls Unitary Products

Page 36
Image 36
Johnson Controls TM9V*MP installation manual Heating Cycle, Troubleshooting, Furnace Control Diagnostics

TM9V*MP specifications

Johnson Controls has long been a leader in providing innovative comfort solutions, and their TM9V*MP series of variable speed air handlers is a testament to their commitment to efficiency and performance. These products are designed to optimize heating and cooling in both residential and commercial applications, ensuring superior indoor air quality and comfort year-round.

One of the standout features of the TM9V*MP series is its variable speed technology. Unlike traditional single-speed systems, the TM9V*MP adjusts its airflow according to real-time heating and cooling demands. This not only enhances comfort by maintaining consistent temperatures but also significantly reduces energy consumption. The variable speed motor operates quietly and efficiently, making it ideal for both living environments and workplaces.

In terms of design, the TM9V*MP is engineered for ease of installation and maintenance. It comes in a compact size that allows for flexible positioning within existing ductwork, making retrofits simpler for contractors. Additionally, the modular design allows for easy access to internal components, which facilitates hassle-free servicing and maintenance.

The unit also features a robust filtration system that works in tandem with a range of air quality technologies. This includes optional media filters that capture allergens and particulates, ensuring that the air quality within a space is not only comfortable but also healthy. The integration of advanced technologies, such as integrated Wi-Fi capabilities, provides users with the ability to monitor and adjust settings remotely via smartphones or tablets.

Moreover, the TM9V*MP series is compatible with a wide range of communication protocols, enabling seamless connectivity with smart home systems. This means that users can create customized comfort profiles and take advantage of energy-saving features automatically.

Durability is another key characteristic of the TM9V*MP series. Built with high-quality materials and subjected to rigorous testing, these air handlers are designed to endure even the most demanding conditions while providing reliable performance over time.

In summary, Johnson Controls' TM9V*MP series offers an array of features that cater to modern comfort demands. With its variable speed technology, user-friendly design, air quality enhancements, and strong connectivity options, it stands out as a prime choice for both residential and commercial HVAC applications, setting a high standard for efficiency and indoor comfort.