VENT SYSTEM
This furnace is certified to be installed with one of two possible vent configurations.
1.Horizontal vent system. This vent system can be installed com- pletely horizontal or combinations of horizontal, vertical, or offset using elbows.
2.Vertical vent system. This vent system can be installed completely vertical or a combination of horizontal, vertical, or offset using elbows.
VENT APPLICATIONS AND TERMINATION
When selecting the location for a combustion air / vent termination, the following should be considered:
1. | Observe all clearances listed in vent clearances in these instruc- |
| tions. |
2. | Termination should be positioned where vent vapors will not dam- |
12” MIN.
12” MIN.
12” Minimum below overhang
12” Minimum separation between bottom of combustion air intake and bottom of vent
Maintain 12” minimumclearance above highest anticipated snow level or grade, whichever is higher
| age plants or shrubs or air conditioning equipment. |
3. | Termination should be located where it will not be affected by wind |
| gusts, light snow, airborne leaves or allow recirculation of flue |
| gases. |
4. | Termination should be located where it will not be damaged or |
| exposed to flying stones, balls, etc. |
5. | Termination should be positioned where vent vapors are not objec- |
| tionable. |
6. | Horizontal portions of the vent system must slope upwards and be |
| supported to prevent sagging. |
7. | Direct vent systems must be installed so the vent and the combus- |
| tion air pipes terminate in the same atmospheric zone. Refer to Fig- |
| ures 31 or 32. |
Maintain 12” minimum clearance above highest anticipated snow level. Maximum 24” above roof.
12” Min.
12” Min.
FIGURE 30: Termination Configuration - 1 Pipe
FIGURE 32: Termination Configuration - 2 Pipe Basement
VENTING MULTIPLE UNITS
Multiple units can be installed in a space or structure as either a single pipe configuration or a
The combustion air side of the single pipe configuration shown in Figure 30 is referred to in these instructions as ambient combustion air supply. Follow the instructions for ambient combustion air installations, paying particular attention to the section on air source from inside the building. The vent for a single pipe system must be installed as specified in the venting section of these instructions with the vent terminating as shown in Figure 30. Each furnace must have a separate vent pipe. Under NO circumstances can the two vent pipes be tied together.
The combustion air side of the
VENT
Maintain 12” minimum clearance above highest anticipated snow level.
12” vertical separation |
| |
between combustion air | 12” minimum | |
intake and vent. | ||
below overhang | ||
| ||
| 12” minimum | |
| separation between | |
| bottom of | |
| combustion air pipe | |
| and bottom of vent. | |
| Maintain 12” | |
| minimum clearance | |
| above highest | |
| anticipated snow | |
| level or grade, | |
| whichever is higher. |
COMBUSTION AIR
2”
MIN.
FIGURE 33: Double Horizontal Combustion Air Intake and Vent Termination
MIN.6”
FIGURE 31: Termination Configuration - 2 Pipe
FIGURE 34: Double Vertical Combustion Air Intake and Vent Termination
26 | Johnson Controls Unitary Products |