Johnson Controls TM9V*MP UIM-C-0712, Combustion Air Source From Outdoors, Free Area

Models: TM9V*MP

1 40
Download 40 pages 32.39 Kb
Page 28
Image 28
Combustion Air Source From Outdoors

701379-UIM-C-0712

This type of installation requires that the supply air to the appliance(s) be of a sufficient amount to support all of the appliance(s) in the area. Operation of a mechanical exhaust, such as an exhaust fan, kitchen ventilation system, clothes dryer or fireplace may create conditions requiring special attention to avoid unsatisfactory operation of gas appliances. A venting problem or a lack of supply air will result in a hazardous condition, which can cause the appliance to soot and gen- erate dangerous levels of CARBON MONOXIDE, which can lead to serious injury, property damage and / or death.

An unconfined space is not less than 50 cu.ft (1.42 m3) per 1,000 Btu/ hr (0.2928 kW) input rating for all of the appliances installed in that area.

Rooms communicating directly with the space containing the appli- ances are considered part of the unconfined space, if doors are fur- nished with openings or louvers.

A confined space is an area with less than 50 cu.ft (1.42 m3) per 1,000 Btu/hr (0.2928 kW) input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combus- tion and ventilation in confined spaces.

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con- sideration in calculating free area. If the free area of a specific louver or grille is not known, refer to Table 12, to estimate free area.

Table 12: Estimated Free Area

 

 

 

Wood or Metal

Wood 20-25%*

Louvers or Grilles

Metal 60-70% *

Screens+

1/4” (6.4 mm)

mesh or larger 100%

 

* Do not use less than 1/4” (6.4 mm) mesh

+Free area of louvers and grille varies widely; the installer should follow louver or grille manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1.The free area of a supply air opening shall be calculated by sub- tracting the blockage area of all fixed louvers grilles or screens from the gross area of the opening.

2.Apertures in a fixed louver, a grille, or screen shall have no dimen- sion smaller than 1/4” (6.4 mm).

3.A manually operated damper or manually adjustable louvers are not permitted for use.

4.A automatically operated damper or automatically adjustable lou- vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position.

When a Category I furnace is removed or replaced, the original vent- ing system may no longer be correctly sized to properly vent the attached appliances.

An improperly sized vent system can cause CARBON MONOXIDE to spill into the living space causing personal injury, and or death.

Table 13: Unconfined Space Minimum Area

 

BTUH Input Rating

Minimum Free Area Required for Each Opening

 

40,000

 

 

40 in2 (258 cm2)

 

 

60,000

 

 

60 in2 (387 cm2)

 

 

80,000

 

 

80 in2 (516 cm2)

 

 

100,000

 

 

100 in2 (645 cm2)

 

 

120,000

 

 

120 in2 (742 cm2)

 

Table 14: Free Area

 

 

 

 

 

 

 

 

 

Minimum Free Area Required for Each Opening

 

BTUH Input

 

Horizontal Duct

Vertical Duct or

Round Duct

 

Rating

 

Opening to Outside

 

 

(2,000 BTUH)

(4,000 BTUH)

 

 

 

 

 

(4,000 BTUH)

 

 

40,000

 

20 in2 (129 cm2)

10in2 (64cm2)

4” (10 cm)

 

60,000

 

30 in2 (193 cm2)

15 in2 (97 cm2)

5” (13 cm)

 

80,000

 

40 in2 (258 cm2)

20 in2 (129 cm2)

5” (13 cm)

 

100,000

 

50 in2 (322 cm2)

25 in2 (161 cm2)

6” (15 cm)

 

120,000

 

60 in2 (387 cm2)

30 in2 (193 cm2)

7” (18 cm)

 

 

 

EXAMPLE: Determining Free Area.

 

 

 

 

Appliance 1 Appliance 2 Total Input

 

 

100,000 +30,000 = (130,000 ÷ 4,000) = 32.5 Sq. In. Vertical

 

 

 

Appliance 1 Appliance 2 Total Input

 

 

100,000 +30,000 = (130,000 ÷ 2,000) = 65 Sq. In. Horizontal

 

 

Gas

Gable

 

Vent

Vent

Ventilated

 

 

 

Optional

Attic

 

Top Above

 

Inlet (a)

 

Insulation

 

 

 

Soffit

Outlet

 

Vent

Air (a)

rnaceuF

 

Gas

 

 

 

Water

 

 

Heater

 

 

Ventilated

 

 

Crawl Space

 

 

 

Gas

 

 

 

 

Gable

Vent

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

Ventilated

 

 

 

 

 

Attic

 

 

 

 

 

Top Above

 

 

 

 

 

Insulation

 

 

 

 

Soffit

 

 

 

Outlet

 

Vent

 

 

 

 

 

 

 

Air (b)

 

 

 

 

 

 

 

Heater

Furnace

Inlet

Inlet

Heater

 

Gas

 

 

 

Gas

Inlet

Water

 

 

 

Water

 

 

 

 

 

Air (b)

 

 

Air (a)

Air (b)

 

Gas

Vent

 

Outlet

 

Air (a)

Furnace

Inlet

 

 

Air (a)

FIGURE 38: Outside and Ambient Combustion Air

Air Supply Openings and Ducts

1.An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction. The opening shall be located within 12” (30.5 cm) horizontally from, the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK” in these instructions for additional information and safety check procedure.

2.The duct shall be either metal, or a material meeting the class 1 requirements of CAN4-S110 Standard for Air Ducts.

3.The duct shall be least the same cross-sectional area as the free area of the air supply inlet opening to which it connects.

4.The duct shall terminate within 12” (30.5 cm) above, and within 24” (61 cm) horizontally from, the burner level of the appliance having the largest input.

5.A square or rectangular shaped duct shall only be used when the required free area of the supply opening is 9 in2 (58.06 cm2) or larger. When a square or rectangular duct is used, its small dimen- sion shall not be less than 3” (7.6 cm).

28

Johnson Controls Unitary Products

Page 28
Image 28
Johnson Controls TM9V*MP UIM-C-0712, Combustion Air Source From Outdoors, Dampers, Louvers and Grilles Canada Only