Jotul GF3 DVII manual Simpson Dura-VentChimney Conversion Kit, Mobile Home Installation

Models: GF3 DVII

1 28
Download 28 pages 45.42 Kb
Page 11
Image 11
Simpson Dura-Vent Chimney Conversion Kit

Simpson Dura-Vent Chimney Conversion Kit

The GF3 DVII Allagash is approved for use with Simpson Dura-vent Chimney Kit as shown in Figure 9. These installation requirements must be followed:

1.In masonry chimney a fireclay liner must be present the entire length of the chimney.

2.The liner must have an inside dimension of 6” round or greater. (USE KIT #934)

3.Prefabricated chimneys must be listed for the specific Simpson Dura-Vent Chimney Conversion Kit or a UL 103 listing. (USE KIT #931, #932, or #933)

4.When venting immediately off the rear of the Allagash the maximum horizontal must be less than 14” (including thimble depth). Any other horizontal must be less than 24“.

5.Restrictor plates, shipped with the stove, should be installed according to the assembly instructions in this manual.

Mobile Home Installation

The Allagash can be installed for use in a mobile home in the U.S. and Canada provided:

1.The stove is secured to the floor of the mobile home. Use Floor Mounting Kit #750304.

2.The stove is installed in accordance with Title 24 CFR, Part 3280- Manufactured Home Construction and Safety Standard, in the U.S. and in Canada, comply with CSA Z240.4, Gas Equipped Recre- ational Vehicles and Mobile Housing.

3.Always contact your local officials about installa- tion restrictions and requirements in your area.

This appliance may be installed as an OEM Iinstallation in manufactured (mobile)homes and must be installed according to the manufacturer’s instructions and the manufactured home construc- tion and safety standard, Title 24 CFRAND SAFETY STANDARD,TITLE 24 CFR, Part 3280. This appliance is only for use withthe type of gas that is indicated on the stove Rating Plate. A gas conversion kit is pro- vided with the GF3 DVII Allagash gas stove.

This appliance may be installed in an aftermarket permanently located, manufactured, (mobile) home, where not prohibited by local codes.

Cetappareilpeutetreinstalledansunmaison prefabriquee(mobile)dejainstalleeademeuresiles reglements locaux le permettent. Cet appareil doit etre utiliseuniquementaveclestypesdegasindiquessurla plaquesignaletique.Nepasl’utiliseravecd’autresgassauf siunkitdeconversioncertifieestinstalle.

￿￿￿"￿$

 

 

"

￿￿￿￿￿.

￿￿￿￿￿￿￿￿￿￿!￿

 

 

 

 

 

￿￿￿￿￿￿￿￿￿￿￿￿#￿￿￿￿￿￿

4

 

 

 

 

￿&￿￿￿￿%￿￿￿#￿

 

 

%￿

 

 

 

 

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿!￿

 

 

￿

 

"

 

￿#￿￿￿￿

 

 

0

 

 

￿￿￿￿￿￿￿*￿

 

￿￿'$￿￿(￿

￿￿￿￿

 

 

 

 

 

 

*+,%￿-!￿

 

 

**

 

 

 

 

#

 

 

 

￿￿$￿￿￿#￿￿

 

 

)(￿￿￿

 

￿#￿

 

3

 

 

"￿

"￿!

 

 

 

 

2￿

 

 

 

 

 

 

*￿"￿￿

 

/0

 

 

 

 

 

￿(￿￿

$￿￿#

 

 

-$￿

 

￿￿2￿￿￿￿￿!￿

 

$1

 

 

 

 

 

 

 

 

 

 

 

"￿￿￿￿￿((￿$￿￿￿'￿￿￿￿￿￿￿￿￿￿￿￿($2

 

$￿

 

 

 

 

Figure 9. GF 3 DVII Allagash vent connection using Simpson Dura-Vent Chimney Conversion Kit.

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY AS AN AIR INTAKE IS NOT COVERED UNDER THE ANSI Z21.88-1999-CSA

2.33-M99 TEST METHODS AND RESULT-

ING ITS/WHI PRODUCT CERTIFICA- TION. THE CODE AUTHORITY HAVING JURISDICTION MUST BE CONSULTED PRIOR TO PROCEEDING WITH THIS INSTALLATION METHOD.

9

Page 11
Image 11
Jotul GF3 DVII manual Simpson Dura-VentChimney Conversion Kit, Mobile Home Installation