Clearance Requirements
Minimum clearances for the GF3 DVII Allagash
Rear: 4” / 102 mm
Ceiling: 12” / 305 mm
Corner: 4” / 102 mm
Right Side: 4” / 102 mm
Left Side: 10” / 254 mm (required for complete access of the lighting instructions)
Minimum Clearance for Vent Pipe
Horizontal Runs: |
|
|
Off the top of the pipe: |
| 2" (50mm) |
Off the sides and bottom: | 1" (25 mm) | |
Vertical Runs, all sides: 1" (25 mm) |
| |
Alcove Installation |
|
|
Minimum Height off stove top: | 40” / 1006 mm | |
MinimumWidth of alcove: | 38” / 965 mm | |
(Assumes 10” off the left side and 4” off the right | ||
side) |
|
|
Maximum Alcove Depth: | 24” / 607 mm |
Pipe Clearances:
1” on vertical runs
2” off top of horizontal runs, 1” on other sides.
Mantel and Trim Clearances
Mantel or Trim Depth
| 24” / 607 mm |
| 18” / 457 mm |
A | 5” / 127 mm |
| B |
| C |
| Minimum |
| Clearance from |
| the Top Plate |
| A = 12” |
| B = 9” |
| C = 4” |
Figure 1.
Parallel Installation
| 4” | |
| 102 mm | |
Left Side | Right | |
Side | ||
10” | 4” | |
254 mm | ||
102 mm | ||
|
Figure 2. Allow 10” on left side of the appliance for complete access to the lighting instructions and control valve.
Corner Installation | 13 1/2” | |
| ||
| 337 mm | |
4” |
| |
102 mm | 13 1/2” | |
16” | ||
337 mm | ||
406 |
| |
mm |
| |
| 36” | |
| 910 mm | |
27” |
| |
686 mm | 4” | |
| 102 mm | |
This is not a required |
| |
hearth size, although it | 16” | |
is aesthetically | ||
proportional. Assumes | 406 mm | |
the stove is 4” off the |
| |
corners. |
|
Figure 3. Top Exit Centerlines and possible hearth configuration.