Horizontal Venting Requirements

Restrictor Sliders

First Restriction Setting - install screw into the OUTER hole of sliders.

Second Restriction Setting - screw installed into MIDDLE hole of slider.

Figure 5. Vent restrictor settings.

Horizontal Venting Requirements

Follow these guidelines if any part of the installation incorporates a horizontal run or terminates horizontally.

Wall Thimble

#942B

90° Elbow

#990B

24” length

#904B

HorizontalLength

12”Max.

Wall Plate

#940B

55 3/4”

Floor to

centerline of

minimum

vertical rise

NOTE:

SHORT LEGS REDUCE THE HEIGHT BY 2 1/4”.

The maximum horizontal run made directly off the rear of the stove shall be no more than 12" and must then be connected to a 14" snorkel cap (Simpson Dura-vent #982).

The horizontal termination cap must maintain a 3" clearance to any overhead combustible projections exceeding 2 1/2" or less. Maintain 12" clearance from projections exceeding 2 1/2". See Figure 8, page for complete termination clearance information.

Any horizontal run of vent must be level or have a 1/4" rise for every foot of run toward the termination cap.

NEVER ALLOW THE VENTING TO SLOPE DOWNWARD, AS HIGH TEMPERATURES MAY RESULT AND CREATE A HAZARDOUS CONDITION.

Vent Pipe Clearance to Combustible Materials: For all

 

horizontal runs, a 2" top clearance and a 1" side and

 

bottom clearance must be maintained.

Wall Pass-through:A minimum 10" X 10" square cutout

 

is required to maintain proper clearances through

Figure 6. Minimum Vertical Vent - Simpson Dura- Vent part numbers shown.

Simpson Dura-Vent 45°

Elbow #945B

12” Max. Horizontal run into a 14” Snorkel Simpson Dura- Vent (#906B)

Figure 7. Horizontal terminal to corner2.

combustible wall construction. The opening must be

framed in. Simpson Dura-Vent Wall Thimble #942 or

Secure Vent Wall Radiation Shield SV4RSM must be

used for the wall pass-through. Optional decorative

plates are available to finish the interior side of the

wall pass-through.

• IMPORTANT: Follow the vent manufacturer’s installa-

tion instructions provided with each vent component.

• DONOTFILLAIRSPACEWITHANYTYPEOFINSULATION.

• MAINTAIN THE PROPER CLEARANCES TO THE TERMI-

NATION CAP. SEE FIG. 10.

• Do not recess the termination cap into a wall or siding.

• Install a Vinyl Siding Standoff between the vent cap

12” Max. Horizontal run into a 14” Snorkel Simpson Dura-Vent (#906B)

14” Snorkel

Simpson

Dura-Vent

(#982)

Rear Exit

Centerline

243/4” 628 mm

and the exterior wall (Simpson Dura-Vent #950). to

protect vinyl siding from overheating.

Figure 7a. Horizontal terminal directly off stove must use a 14” Snorkel termination.