Vent Termination

Vent Termination

Window

VENTING MUST TERMINATE WITHIN THE SHADED AREAS.

REMINDER #1

Any horizontal runs made directly off the rear of the stove must be 14” or less and connected immediately to a Simpson Dura- Vent 14”snorkel (#982).

REMINDER #2

If more than a 12” horizontal run is needed, A VERTICAL RISE IS REQUIRED FIRST. See chart.

REMINDER #3

For each 90° elbow used, after the first, add 5’ to the initial required vertical rise. See chart.

Maximum 90° Elbows - 3 Maximum 45° Elbows - 4

Max.

35

 

Vertical

 

 

Termination

 

Height

 

 

 

30

 

 

25

Use second

 

restriction

 

 

 

 

setting in this

 

 

shaded area.

 

 

See Page 8

 

20

 

feet

 

Use first restriction setting

in

 

 

for termination in this

RISE

 

 

shaded area. See page 8

VERTICAL

15

 

 

 

 

10

 

Vertical

 

 

Termination

7

 

requires 7 ft.

 

 

 

Min. Rise.

 

 

 

5

 

Horizontal

 

 

Termination

2

 

requires 2 ft.

 

Min. Rise.

 

 

1

5

10

Min./Max.

HORIZONTAL RUN in feet

Horizontal

 

 

with 12” rise

10