Alarm Input

Connect this terminal to sensor devices, such as an infrared sensor, door sensor, metal sensor, manual switch, etc.

Input requirements

No-voltage relay NPN open collector input

Polarity of input detection can be selected using a software

Make/Break (500 ms and above)

Circuit current at low level: 0.3 mA

Applied voltage at high level: 3.3 V

Camera unit

 

 

 

Sensor

DC3.3 V

 

 

 

example (1)

 

 

 

VCC

R

Input 1

 

 

 

 

R

 

or Input 2

OUT

 

3.3 V

0.3 mA

 

 

GND

 

GND

 

(Alarm input equivalent circuit)

 

 

Sensor

 

 

 

 

 

 

 

 

example (2)

 

 

 

 

Relay switch etc.

OUT

GND

Alarm Output

Connect this terminal to annunciating devices, such as annunciators, indicators, lights, buzzers, etc.

Output requirements

Equivalent to NPN open collector output (Set the output put logic via the Internet Explorer)

Allowable applied voltage: DC12 V and below

Allowable inflow current: 50 mA

Momentary (100 ms - 5000 ms) output (Set time via the Internet Explorer )

Image adjustment

When the camera is mounted, adjust the image settings while looking at the actual image.

Mounting the test monitor

Connect the [MONITOR] terminal of the camera to the test monitor to adjust the camera shooting direction, field angle and focus.

TWhen configuring, turn on the power of the camera.

[MONITOR]

terminal

75 K terminated

Test monitor

Camera unit

Output 1 or Output 2

GND

 

annunciating

 

devices

 

DC 12 V

IN

R

GND

 

(Alarm output equivalent circuit)

Note

Connect the GND cable of this camera to the GND of the annunciating device.