iFire and Explosion Hazard

Breathing Hazard - Carbon Monoxide Gas

High attiC:uric or;rice must _ nstalled for epera_on above 2,000 feet (610 m),

Ceatact a qualified installer or service agency

Breathing car_n monoxide eaa cause brain damage o[ d_ath Always read and understand instruction rna_ual

Water heaters covered in this manual have been tested and approved for installation at elevations up to 2,000 feet (610

m)above sea level. For installation above 2,000 feet (610 m), the water heater's Btu input should be reduced at the rate of 4 percent for each 1,000 feet (305 m) above sea level which requires replacement of the burner orifice in accordance with the National Fuel Gas Code ANSI Z223.1/NFPA 54. Contact your local gas supplier for further information.

Failure to replace the standard orifice with the proper high altitude orifice when installed at elevations above 2,000 feet (610 m) could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of the safe limits. This could result in serious injury or death. Contact your local gas supplier for any specific changes that may be required in your area.

iFire and Explosion Hazard

Use joint compound or tape compatible with propane,

Leak test before operating heater.

Disconnect gas piping and shut-off valve before pressure testing system.

Use pipe joint compound or Teflon tape marked as being resistant to the action of petroleum (Propane [L.R]) gases.

The appliance and its gas connection must be leak tested before placing the appliance in operation.

The appliance and its individual shutoff valve shall be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 pound per square inch (3.5 kPa). It shall be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound per square inch (3.5 kPa).

Connecting the gas piping to the gas control valve of the water heater can be accomplished by either of the two methods shown in Figures 19 and 20.

®

TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.

Sediment Traps

Fire and Explosion Hazard

Contaminants in gas lines can cause fire or explosion.

Clean all gas piping before installation.

Install drip leg in accordance with NFPA 54.

Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a drip leg (sometimes called a sediment trap) must be incorporated in the piping. The drip leg must be readily accessible. Install in accordance with the Gas Piping section. Refer to the current edition of the National Fuel Gas Code, ANSI Z223.1/NFPA 54.

A sediment trap shall be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap shall be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. If a tee fitting is used, it shall be installed in conformance with one of the methods of installation, shown in Figures 19 and 20.

GROUND

JOINT

 

 

 

UNION

 

 

 

 

(OPTIONAL)

 

 

 

GAS CONTROL

 

 

 

 

 

3"

MtN.

t

 

 

 

(76.2

mm)

 

 

 

 

FIGURE 19. GAS PIPING WITH FLEXIBLE CONNECTOR.

GROUND

JOINT

I_

 

 

UNION

 

II

 

 

(OPTIONAL)

_

 

K PIPE

GAS CONTROL

 

 

 

 

 

 

 

 

 

 

VALVE

 

 

 

II

ORtPLEG

 

(76.2

mm)_

 

U

(SEDIMENTTRAP)

 

FIGURE 20. GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL.

17