Venting (cont'd)

Installation Instructions (cont'd)

Venting (cont'd)

All vent gases must be completely vented to the outdoors of the

structure (dwelling). Install only the draft hood provided with the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

TO

CHIMNEY

RISE PER LINEAR

1

VENT PIPE INSTALLATION

There must be a minimum of 6" clearance between single wail vent pipe and any combustible material. Fill and seal any clear- ance between single wall vent pipe and combustible material with mortar mix, cement, or other noncombustible substance.

For other than single wall, follow vent pipe manufacturer's clear-

ance specifications. To insure a tight fit of the vent pipe in a

brick chimney, seal around the vent pipe with mortar mix cement.

_,WARNINGI

Failureto haverequired clearancesbetween vent pipingand J

combustiblematerial will result in a fire hazard.

I

Gas Piping

_,WARNING

Hake sure the gassupplied is the same type listed on the model rating plate. The inlet gaspressuremust not exceed 10.5in. water column (2.6kPa)for natural gasor 13 in. water column (3.2kPa) for propane(LR) gas.The minimum inlet

gaspressurelistedon the model rating plate is for the pur- poseof inputadjustment.

_,WARNING

If the gascontrol valveissubected to pressuresexceeding½ poundper squareinch(3.5kPa), the damageto the gascon-

tro valvecouldresult in a fire or explosionfrom lealdnggas.

_, WARNINGJ

IIf the main gasline shutoffservingall gasappliances is used J

Jo turn OFF the.gasat eachappliance..Leaveall. gasapph-

Jancesshutoff untJIthe water heater nstallatmnmcomplete. J

A gas line of sufficient size must be run to the water heater. Consult the latest edition of National Fuel Gas Code ANSI

Z223.1, also referred to as NFPA 54 and the gas company con- cerning pipe size.

There must be:

A readily accessible manual shut offvalve in the gas supply line serving the water heater, and

A drip let (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

&WARNINGI

Be surevent pipeisproperly connectedto preventescapeof

dangerousflue gaseswhichcouldcausedeadlyasphyxation.

_,WARNING

Chemical vapor corrosionof the flue and vent system may occurif air for combustioncontainscertain chemicalvapors. Spray can propellants,cleaningsolvents,refrigerator and air conditioner refrigerants, swimming pool chemicals,calcium and sodiumchloride,waxes,bleach,and processchemicalsare typicalcompoundswhichare potentiallycorrosive.

A flexible gas connector or a ground joint union between the shutoffvalve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before li8hting the water heater. Use a soapy water solution, not a match or open flame. Rinse offsoapy solution and wipe dry.

Standard Models are for installation up to 3,300 feet above sea level.

High Altitude Models are for installation from 3,300 to 5,500 feet above sea level.

Ifa standard model is installed above 3,300 feet or a high altitude model is installed, above 5,500 feet, the input rating must be reduced at the rate of 4 percent for each 1,000 feet above sea level.

Contact your local Sears Service Center or gas utility for further information.

The appliance and its gas connection must be leak

_, WARNINGtested

beforeplacingthe appliancein operation.