In many installations it may be desirable to install louvers in the inlet and outlet openings. Louvers may be either stationary or movable. In areas of great temperature variation, it is often best to install movable louvers that can be thermostatically adjusted to regulate air flow and room temperature. See Figure
If the set is to be installed in an atmosphere highly contaminated with impurities such as dust, chaff, etc., it may be necessary to install a filter in the inlet opening.
The following are minimum air inlet and outlet recommendations:
1.If louvers are used, the size of the opening should be increased approximately 50%.
2.If window screening is used, the opening should be increased approximately 80%.
3.If furnace filters are used, the opening should be increased 120%.
4.2 Air-Cooled Generators
0.25cu. ft. x 5 kW = 1.25 cu. ft. (0.023 m2 x 5 kW = 0.115 m2)
Air requirements are listed in each model’s specification sheet. Remember to increase the size of openings for louvers, screens, filters, etc. as described earler in this section.