7.5 Automatic Transfer Switches
A typical standby system has at least one automatic transfer switch connected to the generator set output to automatically transfer the electrical load to the generator set if the normal source fails. When normal power returns, the switch transfers the load back to the normal power source and then signals the generator set to stop.
The transfer switch uses a set of contacts to signal the engine/generator to start. These contacts are terminals 3 and 4 on the generator set controller terminal strip or controller connection terminal strip (if used) inside the junction box. When the normal source fails and the generator set master switch is in the AUTO position, the transfer switch contacts close to start the generator set.
The location of the transfer switch contacts is usually near the contactor with an engine start decal to identify the correct terminals. The terminals are identified as 3 and 4 (or 57 and 58). Do not connect to terminals 57 and 58 on the inner panel circuit board. Connection must be at the contactor location. Verify the correct engine start terminals using the transfer switch wiring diagrams before making connections.
7.6 Control Connections
Most standby generators can be equipped with a myriad of optional equipment that will have to be connected to other components in the system. These accessories will enable the generator set to meet standards for local and national codes, or specific requirements of the customer’s installation. A few of the more common accessories and their functions are listed on the following pages.
7.7 Remote Annunciator
The remote annunciator allows monitoring of the standby power system from a location remote from the generator set. Individual lamps identifying fault shutdowns and/or prealarms are located on the remote annunciator, along with an alarm horn and silence switch. There are both surface- and
|
| Remote Annunciator |
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| ||||||||||||||||||
|
|
| 42A | 2 | K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10 K11 K12 K13 K14 |
| |||
|
|
|
| INPUT | CONTACT RATINGS: 10A @120VAC RESPCB. LOADASSY |
|
| |||||||||||
|
|
|
|
|
|
|
|
| .01A @28VDC MIN. | LOT NO. |
|
|
| |||||
|
|
|
|
|
|
|
|
|
| 10A @28VDC MAX. |
|
|
| |||||
NO C NO | C NO | C NO C | NO C NO C NO | C NO C |
|
| NO C | NO C | NO C NO C NO C | |||||||||
K1 | K2 | K3 | K4 |
| K5 |
| K6 |
| K7 |
|
| K8 | NOK9C K10 | K11 | K12 K13 | K14 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| N |
|
|
|
|
|
| 42B |
|
|
|
|
|
|
|
| P |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| P |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure
7.8 Audiovisual Alarm
The audiovisual alarm warns the operator of a fault shutdown or prealarm condition at a remote location. See Figure
Front View | Side View |
Figure
38 Section 7 Electrical Requirements |