Section 3 Location

Section 3 Location

3.1 Location Factors

Location is the key to a proper installation. The following sections will deal with the factors to consider in a proper installation. Before final plans are made for locating a generator set, the following questions should be raised concerning the set and the proposed site.

1.Is the structure strong enough to support the set and related equipment such as fuel storage tanks, batteries and radiators?

2.Can vibration be effectively isolated and dampened to reduce noise and prevent damage?

3.Is the area clean, dry and not subject to flooding?

4.Is the area large enough to provide easy access for servicing and repair?

5.Can adequate ventilation be attained in the area with a minimum amount of ductwork?

6.Can exhaust gases be expelled safely out of and away from the structure and other buildings?

7.Will an adequate supply of fuel be available to sustain operation during emergencies?

8.Will fuel tank location be within the vertical lift capabilities of the fuel pump?

The location of the generator set must:

DMeet applicable fire rating codes and standards.

DPosition the generator set over a noncombustible surface. If the mounting surface directly under or near the generator set is porous or deteriorates from exposure to engine fluids, construct a containment pan for spilled fuel, oil, coolant, and battery electrolyte. Do not allow accumulation of combustible materials under the generator set.

3.2 Weight

The weight of the generator set will determine the type of construction at the site. Most sets are mounted on concrete at ground level. Some, however, are located on upper levels of steel, concrete or wood construction.

The generator’s weight will determine how strong this construction should be. Generator weights can be found in the specification sheet for your particular model. Be sure that the weight of accessory items is added to the total requirements. This is especially important in upper story or roof installations.

TP-5700 7/93

Section 3 Location

7