Enabling the Relays

Use the [6]=ENABLE CIRCUITS function to enable or disable the master clock’s control relays during circuit wiring or maintenance. This function can also hold back clocks to manually adjust for daylight saving time in the fall if the daylight saving function is not in use (see Setting Daylight Saving Time on page 2-7). The ENABLE CIRCUITS function only enables the relays; it does not turn them on. See Manually Activating Bell Controls on page 2-6to turn on the relays.

Enter the administrative password as shown on page 2-2,then follow the key sequences below:

Press

Display

[#]

SELECT FUNCTION CODE

[6]

[6]=ENABLE CIRCUITS

[#]

SELECT ACTIVE

 

BELL ZONES 12345678

 

CLOCK CKTS

 

PRESS [#] IF CORRECT

[1]...[8]

Enter the circuit numbers that you want to enable or disable by

 

toggling the numbers; when you see all the circuits you want

 

enabled on the display, press [#].

[#]

PRESS [#] TO CONFIRM

2-4

24A715/24A715M Master Clock Installation Manual