During normal operation, 120Vac is applied between the run motor and common lines to operate the clocks until the 58th minute. At HH:58:00 of each hour, the 120Vac is replaced by 120Vdc between the correction and common lines for a period of 200ms, with the common line being positive. This pulse initiates hourly corrections for clocks that are less than 60 minutes slow. At 5:58:09 AM and PM, an additional 120Vdc, 200ms pulse is transmitted to correct clocks that are 60 or more minutes slow.
X = Normally open contact
I = Normally closed contact
1= V250LA4 MOV or equal
2= Diode bridge, 200V min PIV, avg current = # clocks x 0.115A
RELAY |
|
| RELAY |
|
|
|
| ||
|
| K5 (K7) |
|
|
|
| |||
K6 (K8) |
|
|
|
|
|
|
|
| |
| x |
| x | I |
| I |
|
|
|
|
|
|
|
| x |
|
|
| |
CLK1 OR CLK2 |
|
|
|
|
|
|
| MASTER CLOCK |
|
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | FIELD CONNECTIONS | |
|
|
|
|
|
|
|
| ||
10 ASB MAX. |
|
|
|
|
|
|
| WHT | COMMON |
|
|
|
|
|
|
|
| ||
120Vac |
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| BLK | RUN MOTOR |
|
|
|
|
|
|
|
|
| |
AC RTN |
|
|
|
|
|
|
| 1 |
|
|
|
|
|
|
|
| RED |
| |
|
|
|
|
|
|
|
| CORRECTION | |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
| + |
|
|
|
2 –
Figure
Edwards Synchronous Wired Clocks, Type E1
24A715/24A715M Master Clock Installation Manual |