TABLE C

TABLE C

H Maximum

V Minimum

 

 

 

 

feet

(meters)

feet

(meters)

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + H = 40 feet (12.2 m) Max.

H = 20 ft. (6.096 m) Max.

Example: If 20 feet of (H) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1 (V) to 5

(H)ratio. For every 1 foot of

(V)vertical, you are allowed 5 feet of (H) horizontal run, up to a maximum horizontal run of 20 feet.

*Use Firestop/Spacer SV4.5HF or SF4.5HF when using Secure Vent or Secure Flex respectively. Use Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35/40/45 with a center line lower than 48” (1219 mm) above the fireplace top wrapper surface. In all cases the firestop/spacer provided with the termination may be used with the termination, frame to 5” clearance where applicable.

H

H

V

*Wall

Support Bracket

**Wall

Firestop/Spacer

*When using Secure Flex, use

*Ceiling

 

Firestop/Spacer

 

Firestop/Spacer SF4.5VF

(SV4.5VF)

 

**Use Firestop/Spacer SV4.5HF or SF4.5HF when using

 

Secure Vent or Secure Flex respectively. Use

 

Firestop/Spacer SV4.5HF5 or SF4.5HF5 when using

 

Secure Vent or Secure Flex on horizontal vent runs for

Support

the MPLDV35/40/45 with a center line lower than 48”

Bracket

(1219 mm) above the fireplace top wrapper surface.

 

In all cases the firestop/spacer provided with the

 

termination may be used with the termination, frame

 

to 5” clearance where applicable.

 

Square termination (SV4.5HT-2) shown.

See Table 3 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 30 - Top Vent - ONE 90 DEGREE ELBOW - ELBOW

CONNECTION NOT DIRECTLY AT APPLIANCE

Firestop/Spacer

H = 28 inches (711 mm) Maximum

Square termination (SV4.5HT-2) shown.

Figure 31 - Top Vent - ONE 90 DEGREE ELBOW -

CONNECTION DIRECTLY AT APPLIANCE

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

19

Page 19
Image 19
Lennox Hearth EN04-VDLPM Table C, H Maximum, V Minimum, feet, meters, 0.305, 0.610, 0.914, 1.219, 1.524, 3.048, 4.572