Lennox International Inc SL280DFV, DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE

Models: DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE SL280DFV

1 60
Download 60 pages 14.92 Kb
Page 38
Image 38

TABLE 21

SL280DFV, Non−Communicating Thermostat with Humidity Control Feature and Two−Speed Outdoor Unit

OPERATING

 

 

 

 

SYSTEM DEMAND

 

 

SYSTEM RESPONSE

SEQUENCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat Demand

 

Relative Humidity

 

Blower

 

System

 

 

 

 

 

 

 

 

 

 

 

 

Step

 

 

 

 

W

 

W

 

 

Compressor

 

CFM

Comments

Condition

Y1

Y2

O

G

 

Status

D

 

 

1

 

2

 

(COOL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO CALL FOR DEHUMIDIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation −

1

On

 

On

On

 

 

 

Acceptable

24

Low

 

70%*

 

Y1

 

 

 

 

VAC

 

Compressor and indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blower follow thermostat

Normal Operation −

 

 

 

 

 

 

 

 

 

24

 

 

 

2

On

On

On

On

 

 

 

Acceptable

High

 

100%

demand

Y2

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASIC MODE (only active on a Y1 thermostat demand)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

1

On

 

On

On

 

 

 

Acceptable

24

Low

 

70%*

ComfortSense® 7000

 

 

 

 

 

 

 

 

 

 

VAC

 

 

 

thermostat energizes Y2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification

2

On

On

On

On

 

 

 

Demand

0

High

 

70%**

and de−energizes D on a

Call

 

 

 

VAC

 

call for de−humidification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRECISION MODE (operates independent of a Y1 thermostat demand)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

1

On

 

On

On

 

 

 

Acceptable

24

Low

 

70%*

 

 

 

 

 

VAC

 

Dehumidification mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

begins when humidity is

Dehumidification

 

 

 

 

 

 

 

 

 

0

 

 

 

2

On

On

On

On

 

 

 

Demand

High

 

70%**

greater than set point

call

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ComfortSense® 7000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermostat will try to

Dehumidification

 

 

 

 

 

 

 

 

 

0

 

 

 

maintain room humidity

1

On

On

On

On

 

 

 

Demand

High

 

70%**

setpoint by allowing the

call ONLY

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

room space to maintain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a cooler room thermostat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setpoint***

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING

 

 

 

 

 

 

 

 

 

 

 

 

BASIC MODE (only active on a Y1 thermostat demand)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

1

On

On

On

On

 

 

 

Acceptable

24

High

 

100%

ComfortSense® 7000

 

 

 

 

 

 

 

 

 

 

VAC

 

 

 

thermostat energizes Y2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification

2

On

On

On

On

 

 

 

Demand

0

High

 

70%**

and de−energizes D on a

 

 

 

 

call for de−humidification

Call

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRECISION MODE (operates independent of a Y1 thermostat demand)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

1

On

 

On

On

 

 

 

Acceptable

24

Low

 

70%*

 

 

 

 

 

VAC

 

Dehumidification mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

begins when humidity is

Dehumidification

 

 

 

 

 

 

 

 

 

0

 

 

 

2

On

On

On

On

 

 

 

Demand

High

 

70%**

greater than set point

call

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification

1

On

On

On

On

 

 

 

Demand

0

High

 

70%**

ComfortSense® 7000

call ONLY

 

 

 

VAC

 

thermostat will try to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maintain room humidity

 

Jumpers at indoor unit with a two stage outdoor unit

 

 

 

 

setpoint by allowing the

 

 

 

 

 

room space to maintain

 

Cut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2)

 

 

 

 

 

 

 

a cooler room thermostat

 

With Condensing unit − Cut W914 (R to DS) on SureLight® board

 

 

With Heat Pump − Cut W914 (R to DS) & W951 (R to O) on SureLight® control

 

setpoint***

ComfortSense® 7000 thermostat to use for this application − Y2081 4 heat / 2 cool *Normal operation first stage cooling blower speed is 70% COOL speed. **Dehumidification blower speed is, reduced to 70% of COOL.

***In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.

Page 38

Page 38
Image 38
Lennox International Inc SL280DFV, DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE installation instructions