BLOWER DATA
SL280DF070V36A BLOWER PERFORMANCE (less filter)
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1 Heating Speed |
|
|
|
|
|
|
|
|
|
|
|
DIP Switch |
| First Stage Heating Speed - cfm |
|
| Second Stage Heating Speed - cfm |
| |||||
Settings |
|
|
|
|
|
|
|
|
|
|
|
+24% |
| 1065 |
|
|
| 1170 |
|
| |||
+18% |
| 1010 |
|
|
| 1115 |
|
| |||
+12% |
| 960 |
|
|
| 1055 |
|
| |||
+6% |
| 910 |
|
|
| 1000 |
|
| |||
Factory Default |
| 860 |
|
|
| 945 |
|
| |||
| 805 |
|
|
| 885 |
|
| ||||
| 755 |
|
|
| 830 |
|
| ||||
| 705 |
|
|
| 775 |
|
| ||||
|
|
| COOLING |
|
|
|
|
|
| ||
1 Cooling Speed |
| First Stage Cooling Speed - cfm |
|
| Second Stage Cooling Speed - cfm |
| |||||
DIP Switch | Low |
| 2 High | Low |
|
| 2 High | ||||
Settings |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
+ | 745 | 870 | 1025 |
| 1075 | 1100 |
| 1240 | 1425 |
| 1515 |
Factory Default | 665 | 780 | 925 |
| 985 | 1015 |
| 1115 | 1305 |
| 1380 |
– | 590 | 690 | 815 |
| 865 | 900 |
| 1025 | 1170 |
| 1250 |
1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL
SL280DF090V48B BLOWER PERFORMANCE (less filter)
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1 Heating Speed |
|
|
|
|
|
|
|
|
|
|
|
DIP Switch |
| First Stage Heating Speed - cfm |
|
| Second Stage Heating Speed - cfm |
| |||||
Settings |
|
|
|
|
|
|
|
|
|
|
|
+24% |
| 1360 |
|
|
| 1500 |
|
| |||
+18% |
| 1285 |
|
|
| 1415 |
|
| |||
+12% |
| 1220 |
|
|
| 1350 |
|
| |||
+6% |
| 1135 |
|
|
| 1285 |
|
| |||
Factory Default |
| 1075 |
|
|
| 1200 |
|
| |||
| 1030 |
|
|
| 1110 |
|
| ||||
| 960 |
|
|
| 1050 |
|
| ||||
| 890 |
|
|
| 975 |
|
| ||||
|
|
| COOLING |
|
|
|
|
|
| ||
1 Cooling Speed |
| First Stage Cooling Speed - cfm |
|
| Second Stage Cooling Speed - cfm |
| |||||
DIP Switch | Low |
| 2 High | Low |
|
| 2 High | ||||
Settings |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
+ | 740 | 905 | 1040 |
| 1220 | 1085 |
| 1330 | 1545 |
| 1730 |
Factory Default | 690 | 820 | 950 |
| 1110 | 990 |
| 1200 | 1400 |
| 1,595 |
– | 610 | 745 | 855 |
| 1005 | 895 |
| 1075 | 1270 |
| 1460 |
1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.
2Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL
Page 35