BLOWER DATA

BLOWER DATA

SL280DF070V36A BLOWER PERFORMANCE (less filter)

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1065

 

 

 

1170

 

 

+18%

 

1010

 

 

 

1115

 

 

+12%

 

960

 

 

 

1055

 

 

+6%

 

910

 

 

 

1000

 

 

Factory Default

 

860

 

 

 

945

 

 

–6%

 

805

 

 

 

885

 

 

–12%

 

755

 

 

 

830

 

 

–18%

 

705

 

 

 

775

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

745

870

1025

 

1075

1100

 

1240

1425

 

1515

Factory Default

665

780

925

 

985

1015

 

1115

1305

 

1380

590

690

815

 

865

900

 

1025

1170

 

1250

1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.

2Factory default setting.

NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT.

First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.

SL280DF090V48B BLOWER PERFORMANCE (less filter)

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1360

 

 

 

1500

 

 

+18%

 

1285

 

 

 

1415

 

 

+12%

 

1220

 

 

 

1350

 

 

+6%

 

1135

 

 

 

1285

 

 

Factory Default

 

1075

 

 

 

1200

 

 

–6%

 

1030

 

 

 

1110

 

 

–12%

 

960

 

 

 

1050

 

 

–18%

 

890

 

 

 

975

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

740

905

1040

 

1220

1085

 

1330

1545

 

1730

Factory Default

690

820

950

 

1110

990

 

1200

1400

 

1,595

610

745

855

 

1005

895

 

1075

1270

 

1460

1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.

2Factory default setting.

NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT.

First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 455 cfm.