Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV

Models: DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE SL280DFV

1 60
Download 60 pages 14.92 Kb
Page 33
Image 33
TABLE 17

NOTE − The off portion of the selected ramp profile also ap-

plies during heat pump operation in dual fuel applications.

TABLE 17

Cooling Mode Blower Speed Ramping

Ramping Option

Switch 9

Switch 10

A (Factory)

Off

Off

B

Off

On

C

On

Off

D

On

On

Ramping Option A (Factory Selection)

DMotor runs at 50% for 30 seconds.

DMotor then runs at 82% for approximately 7−1/2 minu- tes.

DIf demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.

DOnce demand is met, motor runs at 50% for 30 sec- onds then ramps down to stop.

OFF

 

 

 

 

7 1/2 MIN

 

 

100%

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

82% CFM

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2 MIN

 

 

 

1/2 MIN

 

 

50% CFM

 

 

 

50% CFM

COMPRESSOR DEMAND

Ramping Option B

SMotor runs at 82% for approximately 7−1/2 minutes. If demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.

SOnce demand is met, motor ramps down to stop.

 

7 1/2 MIN

100% CFM

 

OFF

82%CFM

OFF

 

 

COMPRESSOR DEMAND

 

Ramping Option C

SMotor runs at 100% until demand is satisfied.

SOnce demand is met, motor runs at 100% for 45 sec- onds then ramps down to stop.

100% CFM

100% CFM

OFF

OFF

 

COMPRESSOR

Manual backgroundDEMAND Manual background 45 SEC.Manual background

Ramping Option D

SMotor runs at 100% until demand is satisfied.

SOnce demand is met, motor ramps down to stop.

OFF

100% CFM

OFF

 

COMPRESSOR

 

DEMAND

Switches 11, 12 and 13 −− Heating Mode Blower Speed −− The switches are factory set to the OFF position which pro- vides normal heat speed. Refer to table 18 for switches 11, 12 and 13 that provided the corresponding increases or de- crease to both high and low heat demand.

TABLE 18

Heating Mode Blower Speeds

Heat Speed

Switch

Switch

Switch

11

12

13

 

 

 

 

 

Increase 24%

On

On

On

 

 

 

 

Increase 18%

On

On

Off

 

 

 

 

Increase 12%

On

Off

On

 

 

 

 

Increase 6%

On

Off

Off

 

 

 

 

Factory Default

Off

Off

Off

 

 

 

 

Decrease 6%

Off

Off

On

 

 

 

 

Decrease 12%

Off

On

Off

 

 

 

 

Decrease18%

Off

On

On

 

 

 

 

Switches 14 and 15 −− Continuous Blower Speed −− Table 19 provides continuous blower speed adjustments that will result from different switch settings.

TABLE 19

Continuous Blower Speed

Continuous

Switch 14

Switch 15

Blower Speed

 

 

 

 

 

28% of High Cool Speed

Off

On

 

 

 

38% of High Cool Speed

Off

Off

(Factory)

 

 

 

 

 

70% of High Cool Speed

On

Off

 

 

 

100% of High Cool Speed

On

On

 

 

 

Page 33

Page 33
Image 33
Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE, SL280DFV TABLE Cooling Mode Blower Speed Ramping