ELECTRICAL CONNECTIONS
MODELS
OUTDOOR
UNIT
1
2
3
ELECTRIC
WIRING DIAGRAM
For electrical connection refer to wiring diagram
in the unit
1Power supply
2Connection indoor unit with outdoor unit
3Sensor connection
1º Remove the front details at the corners and unit cover panel.
2º Remove the filters See picture
|
|
| NUMBER OF WIRES X SECTION |
| |||
|
|
|
|
|
| ||
MODEL | VOLTAGE | COOLING ONLY |
| HEAT PUMP |
| ||
|
|
|
|
|
|
| |
|
| 1 | 2 | 1 | 2 | 3 | |
| 230 V / 1Ph | 3x4mm2 | 4x1,5mm2 | 3x4mm2 | 2 | 2x1,5mm2 | |
2.8 | 6x1,5mm | ||||||
400 V / 3Ph | 5x2,5mm2 | 4x1,5mm2 | 5x2,5mm2 | 2 | 2 | ||
| |||||||
| 6x1,5mm | 2x1,5mm | |||||
| 230 V / 1Ph | 3x4mm2 | 4x1,5mm2 | 3x4mm2 | 6x1,5mm2 | 2x1,5mm2 | |
3 | 230 V / 3Ph | 4x4mm2 | 4x1,5mm2 | 4x4mm2 | 6x1,5mm2 | 2x1,5mm2 | |
| 400 V / 3Ph | 5x2,5mm2 | 4x1,5mm2 | 5x2,5mm2 | 6x1,5mm2 | 2x1,5mm2 | |
4 | 230 V / 3Ph | 4x4mm2 | 4x1,5mm2 | 4x4mm2 | 6x1,5mm2 | 2x1,5mm2 | |
400 V / 3Ph | 5x2,5mm2 | 4x1,5mm2 | 5x2,5mm2 | 6x1,5mm2 | 2x1,5mm2 | ||
| |||||||
5 | 230 V / 3Ph | 4x6mm2 | 4x1,5mm2 | 4x6mm2 | 6x1,5mm2 | 2x1,5mm2 | |
400 V / 3Ph | 5x4mm 2 | 4x1,5mm2 | 5x4mm2 | 6x1,5mm2 | 2x1,5mm2 | ||
|
NOTE: The sections has been calculated to a distance no superior o 50m and a low supply of 10V
12