REFRIGERANT CONNECTIONS

DISTANCES BETWEEN UNITS

To locate the outdoor and the indoor units, refer to the following information.

L: Distance length between both units. 1 = Refrigerant vapour line.

2 = Liquid aspiration line.

OUTDOOR U.

INDOOR U.

2

L

2

1

L

INDOOR UNIT

OUTDOOR U.

OUTDOOR U.

1

1

2

L

INDOOR U.

MODEL

 

2,8

3

4

5

 

 

 

 

 

 

Tube size

Liquid

3/8"

3/8"

3/8"(1)

1/2"

 

Vapour

5/8"(1)

3/4"

3/4"

3/4"

 

 

 

 

 

 

Refrigerant lines sizes

Máx.Vertical

15

15

15

15

Refrigerant lines sizes L

Total vertical

20

25

20

20

+

 

Horizontal

 

 

 

 

Max. number of bends

 

8

12

8

8

If the height length is greater than 5 meters, a siphon suction must be installed on the suction line every 5 meters to ensure that oil return to the compressor.

(1) Use the coupling fittings included in indoor unit for refrigerant connection with outdoor unit..

NOTE: THE REFRIGERANT LINES GAS AND LIQUID, MUST BE INSULATED

For other positions and longer lengths, consult the Lennox Technical Support Department for application

assistance.

The following data will be obtained from that estimation:

Pipe dimensions, Siphon suction, Insulation, Refrigerant charge

18