ELECTRICAL CONNECTIONS AND SYSTEM CONFIGURATION

IMPORTANT

Prior of making the electrical connections, set the switch for heat pump unit or for cooling only

unit.

This unit is valid for operating as a cold only or heat pump application. The unit should be configured

prior to making the electrical connections, by setting the configuration switch as follows:

1

3

Remove the front details at the corners and unit cover panel.

Rolling side

2

DETALLE A

Remove the filters

Sides and carcass

Filters

 

NOTE: THE UNIT LEAVES FACTORY

CONFIGURATED ON COOLING MODE

 

SWICHT

MODEL

CONFIGURATION

1

2

 

COOLING ONLY

OFF

ON

(*)

HEAT PUMP

ON

ON

 

 

 

(*) Configuration from factory.

(1)P.C.B

PCB

SWICHT CONFIGURATION

SWICHT CONFIGURATION

Switch 2

Switch 1

ON OFF

NOTE:

If errors are made during the configuration of the system, switch off the main power supply, set configuration switch in the correct position and then switch the power on.

CONNECTIONS OF OUTDOOR UNITS

-FOR HEAT PUMP UNITS, remove the resistor form the terminal plate and connect the sensor outdoor unit

-FOR COOLING ONLY UNITS, keep connected the resistor.

DON´T TOUCH.

DETAIL B

4

5

4

DETAIL B

 

 

Regleta de terminales, y

5

SENSOR OUTDOOR

conexión de la sonda exterior

 

UNIT

 

 

 

COOLING ONLY

HEAT PUMP

13

Page 15
Image 15
Lennox International Inc WING manual Electrical Connections and System Configuration