MAINTENANCE OF THE UNIT

POSSIBLE PROBLEMS

PROBLEM

 

SOLUTION

 

 

 

 

 

1.- Unit do not work.

• Check electrical supply of the unit.

• Check electrical connexion.

 

• Check the remote controller and parameter works correctly.

 

 

 

2.- The fan of the unit

 

 

works quicker without any

• Check that the filter of the unit is clean.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

• Check electrical connexion.

 

• If the problem persist, check the function of the motor.

 

 

 

3.- Noise on pipe system.

 

 

NOTE: Some noises are

• Check refrigerant charge is correct.

normal when unit stop and

• Was the vacuum done correctly?

￿￿￿￿￿￿

• Check internal temperature, could be quite low.

 

 

 

• Check possible obstructions in the condensate pan, and also out of the pan.

4.- Excess of condensation

• Check correct level of the unit.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

• Check drainage pipe.

 

 

 

• Check the air filter of the indoor unit.

5.- The indoor battery

• Check the level of refrigerant.

• Check strangulation air flow or recirculation.

freeze continuously.

• If the freeze persist the expansion can be obstructed.

 

 

• ¿Is the temperature below 21 º C?

 

• Check indoor temperature sensor.

 

 

 

6.- Unit work perfectly on

• Check if you have configurate correctly the function mode of the unit.

cooling mode, but do not

• Check inverter valve of the outdoor unit.

produce heat on mode heat

• Check the plate PCB to the solenoid inverted valve.

￿￿￿￿

 

 

 

 

 

 

Check that terminal connexion are slack.

7.-External fan stop

Check the motor.

• Check the condenser situation.

 

 

• Check that that the rele of defrost is not activited

 

(Units heat pump).

 

 

 

8.-Excessive pressure of

Check that the external exchanger is not dirty and obstructed.

condensation (Working

Check that there is no condensable gas and air in the refrigerant circuit.

cooling cycle)

Check that the external fan works correctly.

 

Check that the refrigerant charge is correct

 

 

 

9.-Low pressure

Check that the refrigerant charge is correct

Check possible obstruction on the expansion system of the outdoor unit, liquid

condensation.

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

(Working on cooling

Check that air filter is not dirty or wrong function of indoor fan.

cycle)

 

 

 

 

 

10.-Excessive pressure

Check that the refrigerant charge is correct

on return air (Working

Check the situation of inverter valve.

on heat pump)

Check retention valve situation.

 

 

 

11.-Low pressure on

Check that the refrigerant charge is correct

return air. (working

Check possible obstruction on the expansion system of the outdoor unit

on heat pump)

Check that the external fan works correctly.

 

Check the correct function of the defrost thermostat .

 

 

 

28

Page 30
Image 30
Lennox International Inc WING manual Maintenance of the Unit Possible Problems Solution