REFRIGERANT CONNECTIONS

REFRIGERANT CHARGE

OUTDOOR UNITS TYPE KJF-K/ KJB

 

MODEL

 

 

2,8

3

4

5

 

 

(gr.)

(*)

1.650

2.500

2.600

2.600

 

 

 

 

 

 

 

 

 

COOLING

(gr.)

(**)

5

5

5

5

 

ONLY

 

 

 

 

 

 

 

(gr.)

(***)

30

30

30

55

 

 

 

 

 

 

 

 

 

 

 

HEAT

(gr.)

(*)

1.775

2.500

2.800

3.500

 

 

 

 

 

 

 

 

 

 

5

5

5

5

 

PUMP

(gr.)

(**)

 

 

 

 

 

 

 

 

 

 

(gr.)

(***)

45

45

45

105

 

 

 

 

 

 

 

 

OUTDOOR UNITS TIPO KCF-K/ KCB

 

MODEL

 

 

2,8

3

4

5

 

 

(gr.)

(*)

2.255

2.350

3.070

4.950

 

 

 

 

 

 

 

 

 

COOLING

(gr.)

(**)

5

0

5

5

 

ONLY

 

 

 

 

 

 

 

(gr.)

(***)

30

30

30

55

 

 

 

 

 

 

 

 

 

 

 

HEAT

(gr.)

(*)

2.425

2.525

3.400

5.300

 

 

 

 

 

 

 

 

PUMP

(gr.)

(**)

5

0/5

5

5/0

 

 

 

 

 

 

 

 

 

 

(gr.)

(***)

45

45

45

105

 

 

 

 

 

 

 

 

(*)Refrigerant charge R-22 precharge from factory on the outdoor unit.

(**)Meter of installation line where outdoor unit is precharged+charge also to the group

(***) If line is different to meters indicated on table put more or less charge of refrigerant per meter indicated.

EXAMPLE:

If you need to install a group WING 5CFK, with distance of line between indoor and outdoor unit of 6 meter. The refrigerant charge R-407C needed in the installation is:

Charge precharge on outdoor unit

=

5300

 

Charge per line 55gr/m x (6-5)m

=

55

 

Total charge of the installation

=

5355 gr