Troubleshooting Guide

PipingLengthandElevation

Capacity

Pipe Size

Standard

Max.

Max.

Additional

 

 

Length

Elevation

length

Refrigerant

(Btu/h)

Suction

Evap

m(ft)

B m(ft)

A m(ft)

g/m(oz/ft)

 

 

 

 

 

 

 

9k, 12k

Ø12.7mm(1/2")

Ø6.35mm(1/4")

7.5(25)

7.5(25)

15(49)

20(0.22)

 

 

 

 

 

 

 

Indoor unit

B

A

Outdoor unit

A

Indoor unit

Outdoor unit

Outdoor unit

 

Oil trap

A

 

 

B

Indoor unit

 

B

If piping length is more than 16.4ft(5m)

CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability.

Oil trap should be installed every 16.4~23feets (5~7 meters).

Service Manual 55

Page 55
Image 55
LG Electronics LA120HPO, LA090HPO, LA120CPO, LA120HPI, LA120CPI service manual Piping Length and Elevation