Operation

6. Heating Operation Mode(only Heating Model)

The unit will operate according to the setting conditions by the remote controller.

The operation diagram is shown below.

INTAKE AIR TEMP.

 

 

 

 

 

 

 

SETTING TEMP. +6°F

 

 

 

 

 

 

 

(Compressor OFF)

 

 

 

 

 

 

 

 

 

 

A

B

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTING TEMP.

 

 

 

 

 

 

 

(Compressor ON)

 

minimum

 

minimum

 

minimum

 

 

 

10sec.

 

1 min.

 

10sec.

 

INDOOR FAN SPEED

Selecting

Low

OFF

Low

Selecting

Low

OFF

fan speed

fan speed

 

 

 

 

 

 

COMPRESSOR

ON

 

OFF

 

ON

 

OFF

A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the indoor pipe temperature becomes lower than 95°F, indoor fan stops.

B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.

Hot-Start Control

The indoor fan stops until the indoor pipe temperature will be reached at 82°F.

During heating operation, if indoor pipe temperature falls below 78°F fan stops.

The operation diagram is shown below.

INDOOR PIPE

 

1min

 

 

 

TEMP.

 

 

 

 

 

 

 

 

 

 

82°F

 

 

 

 

 

 

 

 

 

 

78°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR FAN SPEED

OFF

LOW

 

Selecting

OFF

 

fan speed

 

 

 

 

 

COMPRESSOR

 

 

ON

 

 

 

 

 

 

 

40Room Air Conditioner

Page 40
Image 40
LG Electronics LA120HPO, LA090HPO, LA120CPO, LA120HPI, LA120CPI Heating Operation Modeonly Heating Model, Hot-Start Control