Site Preparation

Figure 10 Piping connections for 6- and 8-fan Lee-Temp and Quiet-Line Condensers

Access Valve (Hot Gas) on

Condensers (Typ. 2)

Inlet Connection

Upper Headers (Typ.)

Condenser

Liquid

 

Connections,

 

Line

Hot Gas Line

Typical

 

 

Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).

Entering Hot

Gas Line

Leaving

Liquid Line

Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-supplied).

See

Detail

A-A

Position elbow to direct relief

valve downward

Metal

Clamp

Note: Two circuits supplied; single circuit shown for clarity.

 

Isolator

Detail A-A