Operation

5.0 OPERATION

! WARNING

Risk of electric shock. Can cause injury or death.

Disconnect all local and remote electric power supplies before working within. Unit contains potentially lethal electrical voltage.

Only properly trained and qualified personnel may perform repair, maintenance and cleaning operations.

The fans may start unexpectedly. Disconnect power supply before working on unit. Line side of factory disconnect remains energized when disconnect is off. Use a voltmeter to make sure power is turned off before checking any electrical connections or functions.

5.1Startup Checklist

Refer to 4.0 - Checklist for Completed Installation and verify that all installation items have been completed before beginning to start the condenser.

5.2Startup

Locate “Liebert Condensers and Drycoolers Warranty Inspection Check Sheet” (Document # SAFM-8542-54).

Turn the condenser disconnect ON. Indoor units should be turned on and set for cooling to allow operation of condenser.

Check the fans for proper rotation: Clockwise when viewing the unit from the fan guard (top) side. Check that air is being drawn through the coil and discharged out the fan assembly. Some ambi- ent thermostats may need to be temporarily adjusted to lower temperature settings to observe all fans operate. Readjust thermostat settings to correspond to setpoints shown on the electrical schematic supplied with the unit.

Complete “Liebert Condensers and Drycoolers Warranty Inspection Check Sheet” (Document # SAFM-8542-54).

NOTE

This document must be completed and forwarded to your local Liebert sales office to validate warranty.

Contact your local Liebert sales representative or Liebert Air Product Support if you have any questions or problems during unit startup and commissioning.

Local Liebert sales offices and Liebert air product support contacts can be found at www.liebert.com/servicesupport_pages/ServiceSupport.aspx?x=servicesupport or by calling 1-800-LIEBERT.