Liebert 205 251, 83, 104 165 Field Piping Installation, VFD and Fan Speed Control condenser piping

Models: 104 165 1010 205 251 308 415 510 616 830 83

1 44
Download 44 pages 52.38 Kb
Page 31
Image 31

Inspection and Installation

3.9.2Field Piping Installation

One discharge line and one liquid line must be field-installed for each circuit of the indoor unit and the outdoor condenser(s). Dual circuit condensers are available for most dual circuit indoor unit appli- cations. Refer to Figures 22, 23 and 24 below for additional field-installed piping needed at the con- denser. This piping is needed for proper system performance and for installation/interconnecting receivers and head pressure control valves for Lee-Temp systems.

NOTE

Keep the evaporator unit and condenser closed with their factory charge of dry nitrogen while all field piping is installed. Keep the field piping clean and dry during installation, and do not allow it to stand open to the atmosphere.

When all the field interconnecting piping is in place, vent the condenser’s dry nitrogen charge and connect to the field piping. Finally, vent the evaporator unit’s dry nitrogen charge and make its piping connections last.

Follow all proper brazing practices, including a dry nitrogen purge to maintain system cleanliness.

Figure 22 VFD and Fan Speed Control condenser piping

Entering Hot

Gas Line

Leaving

Liquid Line

Fasten liquid and hot gas lines to leg using flat surface clamps with isolators ( field-supplied).

Support field piping separately

to avoid coil damage and loss of charge.

Traps to Extend Above Base of

Coil by a Minimum of 7-1/2" (190mm)

Inverted Traps

(Field Supplied)

 

Metal

See

Clamp

Isolator

Detail

A-A

Detail A-A

 

DPN001065

 

Rev. 0

27

Page 31
Image 31
Liebert 205 251, 104 165, 308 415, 1010, 510 616 830 Field Piping Installation, VFD and Fan Speed Control condenser piping