Site Preparation

2.0SITE PREPARATION

2.1Site Considerations

The condensers should be installed in a location offering maximum security and access for mainte- nance.

Avoid ground-level sites with public access and areas that contribute to heavy snow or ice accumula- tions. Utilize Piggyback condensers whenever interior building locations must be used. To ensure ade- quate air supply, Liebert recommends that condensers be installed in an area with clean air, away from loose dirt and foreign matter that might clog the coil. In addition, condensers should not be located near steam, hot air or fume exhausts. Also, the condensers should be located no closer than 3 feet (1m) from a wall, obstruction or adjacent unit.

The condenser must not be installed in a pit.

The condenser must be installed on a level surface to ensure proper refrigerant flow.

For roof installation, mount the condenser on suitable curbs or other supports in accordance with local codes.

Lee-Temp receiver tanks should be mounted on the condenser legs for proper operation. Remote mounting of tanks must be within 10 feet of the condenser—Contact Liebert Application Engineering Department for assistance.

2.2Dimensions and Weights

Table 1

Condenser shipping weights, dimensions and volume, approximate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Domestic Packaging

 

 

 

Export Packaging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions

 

 

 

 

Dimensions

 

 

Number

Weight

(LxWxH)

Volume

Weight

 

(LxWxH)

Volume

Model

of Fans

lb (kg)

in. (mm)

ft3 (m3)

lb (kg)

 

in. (mm)

ft3 (m3)

*C**083

1

330

(150)

59x30x51

 

415

(188)

 

60x31x52

 

 

 

 

 

 

 

 

 

 

*C**104

1

350

(159)

52 (1.4)

435

(197)

 

56 (1.5)

(1500x760x1300)

 

(1520x790x1320)

 

 

 

 

 

 

 

 

 

DC**063

1

350

(159)

 

 

435

(197)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*C**165

2

490

(222)

 

 

690

(313)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*C**205

2

560

(254)

97x30x51

 

760

(345)

 

98x31x52

 

 

 

 

 

 

 

 

 

 

DC**119

2

490

(222)

86 (2.4)

690

(313)

 

91 (2.5)

(2460x760x1300)

 

(2490x790x1320)

 

 

 

 

 

 

 

 

 

DC**127

2

560

(254)

 

 

760

(345)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC**143

2

655

(297)

 

 

855

(388)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*C**251

3

590

(268)

139x30x51

 

870

(395)

 

140x31x52

 

 

 

 

 

 

 

 

 

 

*C**308

3

760

(345)

123 (3.4)

1040 (472)

 

131 (3.5)

(3530x760x1300)

 

(3560x790x132)0

 

 

 

 

 

 

 

 

 

DC**214

3

885

(401)

 

 

1165 (528)

 

 

 

 

 

 

 

 

 

 

 

 

 

*C**415

4

935

(424)

179x30x51

 

1235 (560)

 

180x31x52

 

 

 

 

 

 

 

 

 

 

*C**510

4

1230 (558)

158 (4.4)

1530 (694)

 

168 (4.5)

(4550x760x1300)

 

(4570x790x1320)

 

 

 

 

 

 

 

 

 

DC**286

4

1185 (537)

 

 

1485 (674)

 

 

 

 

 

 

 

 

 

 

 

 

*C**616

6

1560 (708)

144x36x97

291 (8.3)

2010 (912)

 

145x37x97

301 (8.4)

DC**409

6

1620 (735)

(3660x910x2460)

2070 (939)

 

(3680x940x2460)

 

 

 

 

 

 

 

 

 

 

 

 

 

*CD*830

8

1930 (875)

184x36x97

 

2430

(1102)

 

185x37x97

 

 

 

 

 

 

 

 

 

 

*CD*1010

8

2910

(1321)

372 (10.)

3410

(1548)

 

384 (10.)

(4670x910x2460)

 

(4700x940x2460)

 

 

 

 

 

 

 

 

 

DC**572

8

2575

(1168)

 

 

3075

(1395)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4