Liebert 1010, 83 Refrigerant Planning Values, R-407C refrigerant required, approximate, Receiver

Models: 104 165 1010 205 251 308 415 510 616 830 83

1 44
Download 44 pages 52.38 Kb
Page 16
Image 16

Site Preparation

2.3Refrigerant Planning Values

Planning for the refrigerant requirements of the completed system is the addition of the charges from Indoor Unit, Condenser (including Lee-Temp receiver, if used) and the interconnecting piping. Tables 3 and 4 provide the approximate charge required for the condensers and the interconnecting piping. Consult indoor unit manuals for indoor unit charge requirements.

These values can be used for obtaining adequate refrigerant for the system, but should not be used for final charging. Consult indoor unit manual for charging procedures.

Table 3

R-22 and R-407C refrigerant required, approximate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Approximate R-22 Refrigerant Needed

Approximate R-407C Refrigerant Needed

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Circuit

 

Dual Circuit

Single Circuit

 

Dual Circuit

 

 

lb (kg)

 

lb/circuit (kg/circuit)

lb (kg)

 

lb/circuit (kg/circuit)

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

Lee-Temp

 

 

Lee-Temp

 

Lee-Temp

 

 

Lee-Temp

Condenser

 

FSC or

(includes

FSC or

(includes

FSC or

(includes

FSC or

(includes

Models

 

VFD

receiver)

VFD

receiver)

VFD

receiver)

VFD

receiver)

83

 

5 (2.3)

27

(12.3)

3

(1.4)

15

(6.8)

5 (2.3)

26

(11.8)

3

(1.4)

15

(6.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

104

 

8 (3.6)

39

(17.7)

7

(3.2)

21

(9.5)

8 (3.6)

37

(16.8)

7

(3.2)

20

(9.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

165

 

15 (6.8)

53

(24.0)

5

(2.3)

27 (12.3)

15 (6.8)

50

(22.7)

5

(2.3)

26 (11.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

205

 

20 (9.1)

76

(34.5)

7

(3.2)

38 (17.2)

19 (8.6)

72

(32.7)

7

(3.2)

36 (16.3)

 

 

 

 

 

 

 

 

 

 

 

251

 

19 (8.6)

75

(34.0)

10 (4.6)

38 (17.2)

18 (8.2)

71 (32.23)

10 (4.6)

36 (16.3)

 

 

 

 

 

 

 

 

 

 

308

 

29 (13.2)

113 (51.3)

11 (5.0)

58 (26.3)

28 (12.7)

107 (48.5)

11 (5.0)

55 (24.9)

 

 

 

 

 

 

 

 

 

 

415

 

54 (24.5)

182 (82.6)

15 (6.8)

75 (34.0)

51 (23.1)

173 (78.4)

15 (6.8)

71 (32.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

510

 

72 (32.7)

 

N/A

30

(13.6)

149

(67.6)

68 (30.8)

 

N/A

29

(13.2)

142

(64.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

616

 

N/A

267

(121.3)

27

(12.3)

113

(51.3)

N/A

254

(115.2)

26

(11.8)

108

(49.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

830

 

N/A

 

N/A

30

(13.6)

149

(67.6)

N/A

 

N/A

29

(13.2)

142

(64.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1010

 

N/A

 

N/A

60

(27.2)

154

(69.9)

N/A

 

N/A

57

(25.9)

147

(66.7)

Quiet-Line Condenser Models

 

 

 

 

 

 

 

 

 

 

 

63

 

N/A

39

(17.7)

 

N/A

21

(9.5)

N/A

37

(16.8)

 

N/A

20

(9.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

119

 

N/A

50

(22.7)

 

N/A

27 (12.3)

N/A

48

(21.8)

 

N/A

26 (11.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

127

 

N/A

76

(34.5)

 

N/A

38 (17.2)

N/A

72

(32.6)

 

N/A

36 (16.3)

 

 

 

 

 

 

 

 

 

 

 

 

143

 

N/A

126 (57.2)

 

N/A

64 (29.0)

N/A

120 (54.5)

 

N/A

61 (27.7)

 

 

 

 

 

 

 

 

 

 

 

 

214

 

N/A

161 (73.0)

 

N/A

81 (36.7)

N/A

153 (69.4)

 

N/A

77 (34.9)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

286

 

N/A

196 (88.9)

 

N/A

125

(56.7)

N/A

186 (84.4)

 

N/A

119

(54.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

409

 

N/A

 

N/A

 

N/A

129

(58.5)

N/A

 

N/A

 

N/A

125

(55.8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

572

 

N/A

 

N/A

 

N/A

196

(88.9)

N/A

 

N/A

 

N/A

186

(84.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4

Interconnecting piping refrigerant charge

 

 

 

 

 

 

 

 

Line Size,

R-22, lb/100 ft. (kg/30m)

R-407C, lb/100 ft. (kg/30m)

 

 

 

 

 

 

O.D., in.

 

Liquid Line

Hot Gas Line

Liquid Line

Hot Gas Line

 

 

 

 

 

 

 

 

3/8

 

3.8

(1.7)

3.7

(1.7)

 

 

 

 

 

 

 

 

1/2

 

7.3

(3.3)

6.9

(3.1)

 

 

 

 

 

 

5/8

 

11.7 (5.3)

2.1 (1.0)

11.0 (5.0

2.2 (1.0)

 

 

 

 

 

 

3/4

 

16.6 (7.5)

3.0 (1.4)

15.7 (7.1)

3.1 (1.3)

 

 

 

 

 

 

 

 

7/8

 

24.4

(11.1)

4.4 (2.0)

23.0

(10.4)

4.5 (1.9)

 

 

 

 

 

 

 

 

1-1/8

 

41.4

(18.9)

7.8 (3.5)

39.3

(17.8)

7.8 (3.5)

 

 

 

 

 

 

 

1-3/8

 

63.3

(28.7)

11.8 (5.4)

59.8 (27.1

11.8 (5.4)

 

 

 

 

 

 

1-5/8

 

16.7 (7.6)

16.7 (7.6)

 

 

 

 

 

 

 

 

12

Page 16
Image 16
Liebert 1010 Refrigerant Planning Values, R-407C refrigerant required, approximate, Receiver, Quiet-Line Condenser Models