Table 2

Condenser physical data

 

 

 

 

 

 

 

 

 

 

 

 

 

Number

Number

Connection Size, OD, In.

Net Weight

 

 

 

 

Model #

 

of Fans

of Circuits

Hot Gas

Liquid

lb (kg)

 

 

 

 

 

 

 

Standard Models

 

 

 

 

 

CS*083

 

1

1

7/8

5/8

295

(134)

 

 

 

 

 

 

 

 

CD*104

 

1

2

7/8

1/2

315

(143)

 

 

 

 

 

 

 

 

CS*104

 

1

1

1-1/8

5/8

315

(143)

 

 

 

 

 

 

 

 

CD*165

 

2

2

7/8

5/8

425

(193)

 

 

 

 

 

 

 

 

CS*165

 

2

1

1-1/8

7/8

425

(193)

 

 

 

 

 

 

 

 

CD*205

 

2

2

1-1/8

7/8

495

(225)

 

 

 

 

 

 

 

 

CS*205

 

2

1

1-1/8

7/8

495

(225)

 

 

 

 

 

 

 

 

CD*251

 

3

2

1-1/8

7/8

500

(227)

 

 

 

 

 

 

 

 

CS*251

 

3

1

1-3/8

1-1/8

500

(227)

 

 

 

 

 

 

 

 

CD* 308

 

3

2

1-3/8

1-1/8

670

(304)

 

 

 

 

 

 

 

 

CS*308

 

3

1

1-5/8

1-1/8

670

(304)

 

 

 

 

 

 

 

 

CD* 415

 

4

2

1-3/8

1-1/8

840

(381)

 

 

 

 

 

 

 

 

CS*415

 

4

1

1-5/8

1-1/8

840

(381)

 

 

 

 

 

 

 

CD*510

 

4

2

1-5/8

1-1/8

1188 (539)

 

 

 

 

 

 

 

CD*616

 

6

2

1-5/8

1-1/8

1380 (626)

 

 

 

 

 

 

 

CS*616 1

 

6

1

(2)1-5/8

(2)1-1/8

1380 (626)

CD*830

 

8

2

1-5/8

1-1/8

1750 (794)

 

 

 

 

 

 

 

 

CD*1010

 

8

2

2-1/8

1-5/8

2640

(1197)

 

 

 

 

 

 

 

Quiet-Line Models

 

 

 

 

 

DCS*063

 

1

1

1-1/8

5/8

315

(143)

 

 

 

 

 

 

 

 

DCD*063

 

1

2

7/8

1/2

315

(143)

 

 

 

 

 

 

 

 

DCS*119

 

2

1

1-1/8

7/8

425

(193)

 

 

 

 

 

 

 

 

DCD*119

 

2

1

1-1/8

7/8

425

(193)

 

 

 

 

 

 

 

 

DCS*127

 

2

1

1-1/8

7/8

495

(225)

 

 

 

 

 

 

 

 

DCD*127

 

2

2

1-1/8

7/8

495

(225)

 

 

 

 

 

 

 

 

DCS*143

 

2

1

1-1/8

7/8

515

(234)

 

 

 

 

 

 

 

 

DCD*143

 

2

2

1-1/8

7/8

515

(234)

 

 

 

 

 

 

 

 

DCS*214

 

3

1

1-5/8

1-1/8

840

(381)

 

 

 

 

 

 

 

 

DCD*214

 

3

2

1-1/8

7/8

840

(381)

 

 

 

 

 

 

 

DCS*286

 

4

1

2-1/8

1-1/8

1105 (501)

 

 

 

 

 

 

 

DCD*286

 

4

2

1-1/8

7/8

1105 (501)

 

 

 

 

 

 

 

DCD*409

 

6

2

1-5/8

1-1/8

1380 (626)

 

 

 

 

 

 

 

 

DCD*572

 

8

2

2-1/8

1-1/8

2430

(1102)

 

 

 

 

 

 

 

 

1.Interconnection piping (field-supplied and installed) required. Configure piping for parallel refrigerant flow between condenser sections.

11

Page 15
Image 15
Liebert 308 415, 205 251, 104 165, 1010, 510 616 830 manual Condenser physical data, Quiet-Line Models