Site Preparation

Figure 8 Piping connections for 1-, 2-, 3- and 4-fan Lee-Temp and Quiet-Line Condensers

Hot Gas

Line

Liquid

Line

Fasten liquid and hot gas lines to leg using flat surface clamps with isolators (field-provided).

Support field piping separately to avoid coil damage and loss

of charge.

See Detail A-A

Metal clamp

Isolator

Detail A-A

Inverted Traps (field-supplied) to extend 8" (203mm) above coil base

Entering

Hot Gas Line

Leaving

Liquid

Line

Position elbow to direct relief valve downward

DPN001067

Rev. 0

Figure 9 Piping connections for 6- and 8-fan Fan Speed Condensers

Access Valve (Hot Gas) on

Condensers (Typ. 2)

Inlet Connection

 

 

Upper Headers

Entering

 

(Typ.)

Hot Gas

 

 

 

 

Line

Leaving

 

Condenser

Liquid Line

 

 

 

Connections,

 

Typical

 

Fasten liquid and hot gas lines to leg using flat surface clamps

with isolators (field-supplied).

Inverted traps (field-supplied) to extend above base of coil by a minimum of 7-1/2" (190mm).

 

Metal

See

Clamp

Isolator

Detail

A-A

Detail A-A

 

 

DPN000668

 

Rev. 01