Unpacking the UPS and Site Preparation

2.4Environmental Conditions

Install the Liebert® GXT3indoors in a controlled environment where it cannot be accidentally turned off. Place it on a level, even surface in an area with unrestricted airflow around the unit. The installation location must be free of water, flammable liquids, gases, corrosives and other conductive contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to 40°C (32 -104°F).

See 8.0 - Specifications for acceptable environmental conditions.

NOTE

UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) will reduce battery life.

2.5Access to Area

The area where the Liebert GXT3-10000T220 is to be placed must have sufficient space for installation procedures and for routine maintenance. The UPS is narrow enough to pass through standard doorways.

2.6Floor Loading

Ensure that the floor where the UPS will be installed will support the unit’s weight (see Table 9 for the unit’s weight).

2.7Inventory List

CD containing:

Liebert MultiLink® shutdown software

Configuration Software

User Manual

Terminal Block Communication terminals

Floor-mount brackets

Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)

USB cable

Hardwire terminal block cover plate and mounting screws

Single input bypass jumper

Battery cabinets contain one DC power cable