Table 10 Battery cabinet specifications

Model Number

GXT3-240TBATTCE

Dimensions, W x D x H, in. (mm)

 

Unit

31.5 x 11.81 x 26.57 (800 x 300 x 675)

Shipping

41.8 x 16.7 x 34 (1062 x 426 x 866)

 

 

Weight, lb (kg)

 

Unit

243 (110)

Shipping

309 (140)

 

 

Internal Battery Parameters

 

Type

Valve-regulated, non-spillable, lead acid

Quantity x V

2 x 20 x 12V

 

 

Battery Manufacturer, Part #

CSB HR1234R or Panasonic UP-RW1245

 

 

Temperature Limits, Batteries Only,

32 to 104 (0 to 40)

°F (°C)

 

Backup Time

See Table 11

Environmental

 

Operating Temp, °F (°C)

32 to 80 (0 to 27)

 

 

Storage Temp

5 to 104 (-15 to 40)

 

 

Transportation Temp, °F (°C)

5 to 122 (-15 to 50)

Relative Humidity

0-95% non-condensing

 

 

Operating Elevation

Up to 3281 ft (1000m) at 80°F (27°C) without derating

 

 

Agency

 

Safety

UL 1778, c-UL Listed

 

 

Transportation

ISTA Procedure 1B

 

 

Table 11 Typical battery run times for the Liebert® GXT3-10000T230

Number of Batteries,

 

 

 

 

Load %

 

 

 

 

Battery Cabinets

 

 

 

 

 

 

 

 

 

 

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

 

 

 

 

 

 

 

 

 

 

 

Internal Battery

81

39

22

15

11

8

6

5

4

3

 

 

 

 

 

 

 

 

 

 

 

Internal Battery + 1

190

127

81

60

46

39

32

26

22

18

External Battery Cabinet

 

 

 

 

 

 

 

 

 

 

Internal Battery + 2

316

162

136

106

82

69

52

48

44

39

External Battery Cabinets

 

 

 

 

 

 

 

 

 

 

Approximate discharge times are at 77°F (25°C) with a 100% resistive load.