Specifications
8.0SPECIFICATIONS
Table 9 | Liebert® GXT3™ specifications | ||
|
| ||
Model Rating, VA (W) | 10,000 (9000) | ||
Dimensions, in. (mm) |
| ||
| Unit, W x D x H | 31.5 x 11.81 x 26.57 (800 x 300 x 675) | |
| Shipping, W x D x H | 41.8 x 16.7 x 34 (1062 x 426 x 866) | |
Weight, lb (kg) |
| ||
| Unit | 308 (140) | |
| Shipping | 428 (194) | |
Input AC Parameters |
| ||
Nominal Operating Frequency | 50 or 60Hz (Factory Default = 60) | ||
| Factory Default VAC | 120/208 at 120 degrees | |
|
|
| |
| 120 / 208 / 220 / 240 | ||
|
|
| |
| Operating Voltage Range | 100 - 185 ±5VAC | |
| Without Battery Operation | ||
|
| ||
| Maximum Allowable VAC | 280 | |
| Input Frequency | 40 - 70Hz | |
| Without Battery Operation | ||
|
| ||
| Input Power Connection | BYP, L1, L2, GND | |
Output AC Parameters |
| ||
| Factory Default, VAC | 208 | |
| Output Connections | Hardwire Terminal Block | |
| Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND | ||
|
| ||
| Frequency | 50Hz or 60Hz, Nominal | |
|
|
| |
| Waveform | Sinewave | |
|
|
| |
| Main Mode Overload | >200% for 5 cycles; 151 - 200% for 1 second; | |
| 105 - 130% 1 minute | ||
|
| ||
Battery Parameters |
| ||
| Type | ||
| Quantity x V | 20 x 12V | |
|
|
| |
| Battery Mfr. / Part # | CSB HR1234R or Panasonic | |
|
|
| |
| Backup Time | See Table 11 | |
Recharge Time (Internal Batteries) | 3 hr. to 90% capacity after full discharge into 100% load | ||
|
| ||
Bypass Protection Limits |
| ||
| Maximum Bypass Current | 50A | |
|
|
| |
| Disable Bypass Operation | If input voltage exceeds ±10% of the nominal voltage | |
| If input voltage returns to within ±8% of nominal output voltage | ||
| Disable Bypass Operation | When the input frequency prevents synchronous operation | |
Environmental |
| ||
Operating Temperature, °F (°C) | 32 to 86 (0 to 30) with 0.9 pf | ||
86 to 104 (30 to 40) with 0.8pf | |||
|
| ||
Storage Temperature, °F (°C) | 5 to 122 | ||
Transportation, °F (°C) |
| ||
| Relative Humidity | ||
| Operating Elevation | Up to 3281 ft (1000m) at 80°F (27°C) without derating | |
| Audible Noise | <55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides | |
Agency |
|
| |
| Safety | UL 1778, | |
| RFI/EMI | FCC Part 15, Subpart B, Class A | |
| Surge Immunity | IEC/EN | |
| Transportation | ISTA Procedure 1B | |
|
|
|
25