8.0SPECIFICATIONS

Table 9

Liebert® GXT3specifications

 

 

Model Rating, VA (W)

10,000 (9000)

Dimensions, in. (mm)

 

 

Unit, W x D x H

31.5 x 11.81 x 26.57 (800 x 300 x 675)

 

Shipping, W x D x H

41.8 x 16.7 x 34 (1062 x 426 x 866)

Weight, lb (kg)

 

 

Unit

308 (140)

 

Shipping

428 (194)

Input AC Parameters

 

Nominal Operating Frequency

50 or 60Hz (Factory Default = 60)

 

Factory Default VAC

120/208 at 120 degrees

 

 

 

 

User-Configurable VAC

120 / 208 / 220 / 240

 

 

 

 

Operating Voltage Range

100 - 185 ±5VAC

 

Without Battery Operation

 

 

 

Maximum Allowable VAC

280

 

Input Frequency

40 - 70Hz

 

Without Battery Operation

 

 

 

Input Power Connection

BYP, L1, L2, GND

Output AC Parameters

 

 

Factory Default, VAC

208

 

Output Connections

Hardwire Terminal Block

 

Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND

 

 

 

Frequency

50Hz or 60Hz, Nominal

 

 

 

 

Waveform

Sinewave

 

 

 

 

Main Mode Overload

>200% for 5 cycles; 151 - 200% for 1 second; 131-150% 10 seconds;

 

105 - 130% 1 minute

 

 

Battery Parameters

 

 

Type

Valve-regulated, non-spillable, lead acid

 

Quantity x V

20 x 12V

 

 

 

 

Battery Mfr. / Part #

CSB HR1234R or Panasonic UP-RW1245

 

 

 

 

Backup Time

See Table 11

Recharge Time (Internal Batteries)

3 hr. to 90% capacity after full discharge into 100% load

 

 

Bypass Protection Limits

 

 

Maximum Bypass Current

50A

 

 

 

 

Disable Bypass Operation

If input voltage exceeds ±10% of the nominal voltage

Re-Enable Bypass Operation

If input voltage returns to within ±8% of nominal output voltage

 

Disable Bypass Operation

When the input frequency prevents synchronous operation

Environmental

 

Operating Temperature, °F (°C)

32 to 86 (0 to 30) with 0.9 pf

86 to 104 (30 to 40) with 0.8pf

 

 

Storage Temperature, °F (°C)

5 to 122 (-15 to 50)

Transportation, °F (°C)

 

 

Relative Humidity

0-95% non-condensing

 

Operating Elevation

Up to 3281 ft (1000m) at 80°F (27°C) without derating

 

Audible Noise

<55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides

Agency

 

 

 

Safety

UL 1778, c-UL

 

RFI/EMI

FCC Part 15, Subpart B, Class A

 

Surge Immunity

IEC/EN 61000-4-5, ANSI C62.41 (for North America)

 

Transportation

ISTA Procedure 1B

 

 

 