Technical dataRadar Tank Gauge
| Auxiliary energy |
|
|
Electrical connection | Housing T 12 with separate terminal compartment. |
|
|
Load HART | Minimum load for HART communication: 250 Ω |
|
|
Cable entry | Cable gland: M20x1.5 or Pg13.5 |
| Cable entry: G ½ or ½ NPT |
|
|
Supply voltage | See page 28 |
|
|
Power consumption | Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V. |
|
|
Current consumption | Max. 21 mA (50 mA inrush current). |
|
|
Power supply | For stand alone operation recommended via e.g. Varec RN 221N/Z. |
|
|
| Performance characteristics |
|
|
Reference operating | According to OIML R85: |
conditions | • Temperature = |
| • Atmospheric pressure |
| • Relative humidity (air) = 65 % ±15% |
| • Medium properties: e.g. medium with good reflectivity and calm |
| surface. |
| • Tank diameter: signal beam hits the tank wall only at one side. |
| Note! |
| No major interference reflections inside the signal beam. |
|
|
Maximum measured | Absolute accuracy: 0.5 mm (2σ value) |
error | Inventory Control Versios: ±3 mm |
|
|
Proof of accuracy for | The accuracy of each 7500 RTG is established through a calibration |
custody transfer ver- | certificate that records the absolute and relative error at 10 |
sions | equidistant points during the final test. For stilling well measurements |
| with 7532 RTG, a NMI / PTB calibrated tape with an absolute accuracy |
| of 0.25 mm is used. |
| Each 7500 RTG is delivered with the PTB and NMi type approval. |
| Additional initial factory verifications for custody applications are |
| available on demand for all 7500 RTG. |
|
|
Maximum fill speed | By the first pass trough of measuring range: 100 mm/min., after it |
| unlimited. |
|
|
0,3 mm (1/64") | |
|
|
Hysteresis | 0.3 mm |
|
|
Resolution | digital: 0.1 mm |
| analogue: 0.03 % of measuring range |
|
|
Settling time | Typical 15 sec |
|
|
The | |
|
|
Influence of ambient | Within the specified accuracy according to OIML R85. |
temperature |
|
|
|
Software reliability | The software used in the 7500 RTG fulfills the requirements of OIML |
| R85. This particularly includes: |
| • cyclical test of data consistency |
| • |
| • segmented data storage |
| The 7500 RTG continuously monitor the compliance with accuracy |
| requirements for custody transfer measurements according to OIML |
| R85. If the accuracy cannot be maintained, a specific alarm is |
| generated on the local display and via the digital communication. |
|
|
88 | Installation and Operations Manual |