Lochinvar 495, 065 Combination Gas Valves, Checking Gas Supply Pressure, Table - H, Installation

Models: 000 - 2 065 495

1 52
Download 52 pages 31.23 Kb
Page 18
Image 18
Combination Gas Valves

Hydronic Heating Boilers and Domestic Water Heaters

INSTALLATION

Continued

Water heater models do not have downstream test valves, but the rest of the gas train is represented by Figure 19.

not required to have vent or relief lines piped to the outdoors. The termination of the vent limited opening on the combination gas valve/regulator complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the appliance manufacturer without the installation of additional vent lines.

Combination Gas Valves

These units fire in up to 2 stages of burner input. Each stage of burner operation has a combination gas valve or series of gas valves to cycle the gas supply on and off and regulate gas to the burners. Each combination valve consists of a gas regulator and two valve seats to meet the requirements for redundant gas valves. The valve has a gas control knob that must remain in the open position at all times when the unit is in service. The gas control valve has pressure taps located on the inlet and discharge sides of the valve. Manifold pressure is adjusted using the regulator located on the valve. A manifold gas pressure tap for each burner stage is located on the discharge side of the valve.

The manifold pressure is preset at the factory and adjustment is not usually required. If you must adjust regulator pressure, follow the instructions under Gas Manifold Pressure Adjustment, page 19.

Venting of Combination Gas Valves

The combination gas valve/regulator used on all units is equipped with an integral vent limiting orifice per ANSI Z21.78. The vent limiter ensures that the volume of gas emitted from the valve does not exceed the maximum safe leakage rate allowed by agency requirements. Combination gas valve/regulators equipped with integral vent limiters are

Checking Gas Supply Pressure

Use the following procedure to check gas supply pressure.

1.Turn the main power switch to the "OFF" position.

2.Turn gas valve knobs to the "OFF" position.

3.Shut off gas supply at the field-installed manual gas cock in the gas piping to the unit. If fuel supply is L.P. gas, shut off gas supply at the tank.

4.Remove the 1/8" hex plug, located on “inlet” side of the gas valve. You may also use a tapping on the field-installed main manual gas cock or gas piping. Install a fitting in the inlet pressure tapping suitable to connect to a manometer or magnahelic gauge. Range of scale should be 14" w.c. or greater to check inlet pressure.

5.Turn on gas supply at the manual gas cock, turn on L.P. gas at tank if required.

6.Turn the power switch to the “ON” position.

7.Turn the gas valve knobs to the “ON” position. Set the electronic temperature control or thermostat to call for heat.

8.Observe the gas supply pressure as all burners are firing. Ensure that inlet pressure is within the specified range. See Connecting To Gas Supply, page 16 for minimum and maximum gas supply pressures.

TABLE - H

Multiple Unit Installations Gas Supply Pipe Sizing

Nominal Iron

 

 

 

 

Length of Pipe In Straight Feet

 

 

 

 

Pipe Size,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Inches)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4"

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1"

697

477

384

328

292

267

246

226

210

200

179

164

149

138

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1/4"

1,400

974

789

677

595

543

502

472

441

410

369

333

308

287

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1/2"

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2"

4,100

2,820

2,260

1,950

1,720

1,560

1,440

1,330

1,250

1,180

1,100

974

871

820

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-1/2"

6,460

4,460

3,610

3,100

2,720

2,460

2,310

2,100

2,000

1,900

1,700

1,540

1,400

1,300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3"

11,200

7,900

6,400

5,400

4,870

4,410

4,000

3,800

3,540

3,300

3,000

2,720

2,500

2,340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4"

23,500

16,100

13,100

11,100

10,000

9,000

8,300

7,690

7,380

6,870

6,150

5,640

5,130

4,720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a total system pressure drop of 0.5 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).

18

Page 18
Image 18
Lochinvar 495, 065, 000 - 2 Combination Gas Valves, Checking Gas Supply Pressure, Table - H, Installation, Continued