High-Fire Offset

Installation and Service Manual

High-Fire Offset

The temperature control operates a two-stage firing system. The two stages are High-Fire and Low-Fire. High-Fire operates all burners while Low-Fire operates approximately one-half of the burners.

The High-Fire knob specifies the number of degrees below set point that the High-Fire stage shuts down. At that point, the unit will continue to operate at the Low-Fire stage until the set point is reached.

The High-Fire offset knob has settings between 0°F and 20°F. If set at 0°F, the High-Fire offset is disabled and the unit will operate at the High-Fire stage until the set point is reached and the temperature control shuts the unit off.

When the High-Fire offset knob is set to 0 or 1, the unit will light at Low Fire and operate for approximately 10 seconds before the High-Fire stage actuates. When set to 2 or above, the unit will operate at Low Fire for 2 minutes before the High Fire stage actuates.

Outdoor Air Reset Option

For boilers ordered with the Outdoor Air Reset option, there is an additional control (see Figure 36). There are three setting knobs for Shutdown, Outdoor Air Max., and Ratio. There is also a switch to turn the outdoor air sensor On or Off. An O.A. Sensor is also included.

Shutdown

The Shutdown knob specifies the outdoor air lockout temperature at which the control would prevent the unit from operating. This feature can be enabled/disabled with the O.A. Shutdown switch.

Outdoor Air Max (O.A. Max)

The O. A. Max knob allows a reset up to the maximum outdoor air temperature specified by this knob setting. When the outdoor air temperature is above the specified setting, the unit will not function in the O.A. Reset Mode, but will continue to run at the selected set point temperature.

Note that the set point knob will now indicate the “minimum” boiler temperature. Target temperature is determined by the ratio and outdoor air temperature below the O.A. Max setting.

Ratio

The Ratio knob allows the control over the reset ratio to be used during Outdoor Air Reset. The allowable ratios are as low as 0.5:1 or as high as 1.5:1.

Selecting the 0.5:1 ratio will increase the set point 0.5°F for every 1.0°F drop in outdoor air temperature up to the maximum set point temperature.

Selecting the 1.5:1 ratio will increase the set point 1.5°F for every 1.0°F drop in outdoor air temperature up to the maximum set point temperature.

See Figure 37 for an outdoor air reset chart example.

(c)2002 L.C.

55

 

 

CN1

 

 

CN2

 

CN3

 

 

 

 

 

 

 

 

 

 

OJ1

CN7

 

50

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D4

 

65

O.A. SENSOR

 

 

 

 

 

CN4

C10

CN8

 

 

ON ENABLE

 

 

 

 

 

 

45

 

 

 

 

 

 

 

 

 

 

VR3

 

 

SW1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

70

 

DISABLE

 

 

 

 

 

 

 

 

W1

O.A. SHUTDOWN

 

 

 

 

 

CN5

OJ2

 

SHUTDOWN

 

 

 

 

 

 

 

 

 

 

 

 

R6

R4

C7

 

 

 

 

55

 

 

 

1.0

 

 

 

C9

 

 

 

 

0.9

 

 

 

 

 

CN6

 

 

50

60

 

1.1

 

 

 

 

 

 

 

 

0.8

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

65

0.7

 

1.3

 

 

 

J4

 

 

 

 

 

 

 

 

 

 

W3

 

 

 

 

 

VR1

 

0.6

VR2

1.4

 

 

 

R8

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

40

70

 

1.5

 

 

 

 

 

CN1

 

 

 

W1

W2

 

 

 

 

O.A. MAX.

 

RATIO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN9

 

160

 

 

 

10 11

 

 

 

 

 

 

 

200

9

 

 

 

10

 

 

140

 

8

 

12

 

 

 

 

 

 

 

 

 

 

 

R15

R16

5

 

 

15

 

 

 

 

7

 

13

 

 

 

 

 

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

6

 

14

 

 

 

 

 

 

 

 

 

 

5

VR2

15

 

(F-)0

VR3

20

 

 

 

240

 

 

 

 

OFF

DIFFERENTIAL

 

 

HIGH-FIRE

 

 

SETPOINT

 

TST2314

 

 

 

OFFSET

 

Figure 36 - Optional Outdoor Air Reset Control

31

Page 31
Image 31
Lochinvar 065, 495, 000 - 2 Outdoor Air Reset Option, High-FireOffset, Shutdown, Outdoor Air Max O.A. Max, Ratio